START-UP: Adjustments
GB
Interface
Description
1
+ Button
2
- Button
3
Select Button
4
LEDs
5
Screen
6
RS 232
Principle
The fan unit in casing is supplied with humidity-controlled regulated pressure control (e.g. H130), the H indicating the type
of control (Humidity-controlled regulated pressure) and 130 the pressure in real time, the LED 'Pa' is lit.
Maximum pressure adjustment (+ and - buttons):
The + and – buttons allow you to modify the maximum pressure value within the type of adjustment selected (C, A, H or F),
the Mode LED is lit. After a short period of inactivity the display returns to the form "Type of control + pressure in real
time" e.g. "A130", the Pa LED is lit.
Access via SELECT
Changing the type of control or airflow reading is carried out using the SELECT button.
By pressing SELECT the display format is: type of control + Maximum Pressure (Example: A130)
No. of presses
Regulation mode
1
Constant pressure
2
Self-adjusting regulated pressure
3
Humidity-controlled regulated pressure
Regulated pressure when combined with a T.Flow Hygro system or
4
with a T.Flow Hygro+ system
5
Airflow
The + and – buttons enable to change the maximum pressure value and to confirm data recording. Without any action on
+ and – buttons, no change in the adjustment will be carried out.
After a short period of inactivity or 6 presses on SELECT the display returns to the form "Type of control + pressure in
real time" e.g. "A130", the Pa LED is lit.
Test mode for regulated pressure operation:
After start up and once the maximum pressure has been set, if the regulation mode chosen is either A (self-adjusting regu-
lated pressure), H (Humidity-controlled regulated pressure), or F (regulated pressure when combined with a T.Flow Hygro
system or with a T.Flow Hygro + system), the unit automatically enters Test mode for 24 hours.
The apparatus self-adjusts in order to define its reference (airflow-pressure) curve.
Representation
Function
Increases maximum pressure by 1 Pa by touch pressure
+
Prolonged touch pressure = increases pressure in gusts
2s later, display of the pressure in real time
Decreases maximum pressure by 1 Pa by touch pressure
-
Prolonged touch pressure = decreases pressure in gusts
2s later, display of the pressure in real time
Select
Allows you to choose the type of control (C: Constant pressure, A: self-adjusting regulated
pressure, H: humidity-controlled regulated pressure and F: regulated pressure when combined
with a T.Flow Hygro system or with a T.Flow Hygro+ system) and the reading of the airflow
Indicates the on-going display
Pa
Mode
m
/h
3
Displays the airflow, type of regulation + pressure etc.
Displays the operating faults (E...)
Connection for a lap-top computer
9
Ex: Display
LED lit
C130
Mode
A140
Mode
H150
Mode
F150
Mode
1250
m
/h
3