6. Temperature Detection Circuit
The outdoor unit (this model) provides with the outdoor temperature thermistor, DEF (defrost) thermistor, OH (overheat)
thermistor and electric expansion valve thermistor so that they detect the temperatures of the unit and control the system.
The circuit of the thermistors is shown as Fig. 6-1, and their roles and temperature measuring points are shown as Table 6-1.
The DEF thermistor, OH thermistor and electric expansion valve are for A cycle and B cycle respectively. The outdoor
temperature thermistor is common to A cycle and B cycle.
CN4A XA2P
(white)
OH thermistor A
CN5A XA2P
(blue)
DEF thermistor A
CN6A XA2P
(red)
Outdoor temperature
thermistor A
CN7A XA8P
(white)
Electric expansion valve thermistor
(thin pipe 1) A
Electric expansion valve thermistor
(thick pipe 1) A
Electric expansion valve thermistor
(thin pipe 2) A
Electric expansion valve thermistor
(thick pipe 2) A
CN4B XA2P
OH thermistor B
(yellow)
CN5B XA2P
(black)
DEF thermistor B
CN7B XA8P
(black)
Electric expansion valve thermistor
(thin pipe 1) B
Electric expansion valve thermistor
(thick pipe 1) B
Electric expansion valve thermistor
(thin pipe 2) B
Electric expansion valve thermistor
(thick pipe 2) B
C o n t r o l
Fig. 6-1 Temperature Detection Circuit
226
Micro computer
AX 6N00
Outdoor temperature
Selection
Micro computer
AX 6N00
Outdoor temperature
Selection