GB
2.2 Recommendations for Heat Mode
Maximum water temperature in your appliance
To ensure optimum service life of the components of your appliance, the
temperature of your water supply should be limited to a maximum of 75ºC.
Thermostatic valve (optional, not included)
In heating-only installation, it is possible to add a thermostatic valve to
control the flow of water and thereby the ambient temperature in your room.
2.3 Recommendations for Refresh Mode
Minimum water temperature in your appliance
Condensation may form if the temperature of the cold water used with
your appliance is too low. Be aware that your appliance is not equipped
with any condensation recovery gutter or similar.
Depending on the temperature and pressure in your room, water conden-
sation may develop, and possibly cause corrosion of your radiator and
damage to its built-in fans.
A water supply device with dew point management capability (such as
a Zehnder ComfoBox) will automatically regulate water temperature inside
your appliance with reference to ambient temperature to allow optimum
functioning.
Thermostatic valve
A thermostatic valve must not be used when the appliance is installed to
provide both heating and Refreshing.
Using your appliance