AERASGARD
RCO
Maintenance-free AERASGARD
elegant plastic housing, for determining the CO
standard signal, which is directly presented visually by five coloured LEDs (traffic light indicator). Available in device versions RCO
wall mounting, RCO
-A UPNT for mounting on in-wall flush boxes and RCO
2
The room sensor is used in classrooms, training rooms and convention centres, offices, hotels, apartments, shops, etc. and is used for easy and
quick evaluation of the indoor climate. This enables energy-saving room ventilation on an as-needed basis, thereby reducing operating costs and im-
proving well-being. The CO
measurement is performed using an optical NDIR sensor (non-dispersive infra-red technology).
2

TECHNICAL DATA

Power supply:
Electrical connection:
Sensor:
Measurement range:
Measuring accuracy:
Temperature dependence:
Pressure dependence:
Long-term stability:
Gas exchange:
Ambient temperature:
Warm-up time:
Response time:
Housing:
Dimensions:
Installation:
Protection class:
IP rating:
Standards:
Equipment:
®
AERASGARD
RCO
- A NT
CO
2
2
Type ⁄ WG02
Measuring ranges
CO
2
RCO
-A NT
2
R C O 2 - A N T
0...3000 ppm
R C O 2 - A N T S T
0...3000 ppm
R C O 2 - A U P N T
0...3000 ppm
Note:
This unit must not be used as safety-relevant device!
- A NT
2
®
CO
sensor for schools (RCO
2
content of room air (0...3000 ppm). The measuring transducer converts the measurand to a
2
RCO
-A UPNT: 24 V AC ⁄ DC (± 10 %)
2
RCO
-A NT, RCO
-A NT ST: 230 V AC (50 -60 Hz)
2
2
power supply unit 230 V ⁄ 50 -60 Hz (included in the scope of delivery)
optical NDIR sensor (non-dispersive infrared technology),
with manual calibration (via zero button)
with automatic calibration
0...3000 ppm
typically ± 30 ppm ± 3% of measured value
± 5 ppm ⁄ °C or ± 0.5% of measured value ⁄ °C
(whichever is greater)
± 0.13% ⁄ mm Hg
< 2% in 15 years
by diffusion
0...+ 50 °C
approx. 1 hour
< 2 minutes
plastic, material ABS, colour pure white (similar to RAL 9010)
85 x 85 x 27 mm (Baldur 1)
RCO
-A UPNT, RCO
2
2
on vertically or horizontally installed in-wall flush boxes for cable entry from the back, with predetermined
breaking point for on-wall cable entry from top ⁄ bottom in case of plain on-wall installation
RCO
-A NT ST: mobile CO
2
III (according to EN 60 730)
IP 30 (according to EN 60 529)
CE-conformity, electromagnetic compatibility
according to EN 61 326, EMC directive 2014 ⁄ 30 ⁄ EU,
low voltage directive 2014 ⁄ 35 ⁄ EU
traffic light indicator (five coloured LEDs, see table)
for displaying the CO
2
Connector for power supply unit (connecting cable approx. 1.5 m) or
in-wall power supply unit for mounting on in-wall flush boxes (RCO
Stand holder made from stainless steel (RCO
sensor for schools with traffic light indicator incl. power supply unit
Display
CO
2
5 LEDs
5 LEDs
5 LEDs
-A NT ) with traffic light display, incl. power supply unit, self-calibrating, in an
2
-A NT ST as a floor-mounted device with a metal support.
2
-A NT: wall mounting or on in-wall flush box, Ø 55 mm, base with 4-hole for mounting
measuring instrument on stand holder (table-top unit)
2
concentration
-A NT ST)
2
 Equipment
Connector for power supply unit
Connector for power supply unit, stand holder
In-wall power supply unit
Rev. 0000 - V10
-A NT for direct
2
-A UPNT)
2
Item no.
(Baldur 1)
with traffic light
1501-61A0-7331-232
1501-61A0-7331-231
1501-61A0-7331-233

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Aersagard rco2-a nt stAersagard rco2-a upnt1501-61a0-7331-2321501-61a0-7331-2311501-61a0-7331-233

Table des Matières