Simer 2520ULST Notice D'utilisation page 3

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Installation
Fire and explosion hazard. Do not use this
pump to pump flammable or explosive liquids. Use pump
only with liquids compatible with pump component
materials. Do not use pump in explosive atmospheres.
Risk of flooding. If for any reason property
damage or personal injury can result from an inoperative
or leaking pump, an auxiliary switch backup system
and/or an alarm should be installed with pump.
Pump must be level!
Pump can also be installed
on wall or floor. Allow at least
6-1/2" vertical clearance to
allow tank removal.
Mount pump on side of furnace (or on floor or
1
wall).
INSTALLATION
Electrical shock and carbon monoxide
hazards. When mounting the pump on the side of the
furnace, make sure that the mounting holes clear the
heat exchanger and all wiring. The mounting screw for
the pump should touch only the pump reservoir flange
and the exterior sheet metal on the furnace. If in doubt or
if this is confusing, consult a qualified HVAC serviceman
or the furnace manufacturer.
AC Unit
Condensate
Furnace
Drain
Condensate
Drain
Plastic
Tubing
Run plastic tubing as shown into pump's drain inlet
2
hole(s).
For parts or assistance, call Simer Customer Service at
From A.C.
Unit
Gas
Condensing
Furnace
Mount Pump
below all Heater
and A.C. Drains
5490 0906
A t
l e
a s
t 6
- 1
/ 2
"
Cut tubing at an angle
so that bottom of
reservoir doesn't close it.
Be sure tubing does not
interfere with float.
1-1
1 2
" above
bottom of
reservoir
5491 0906
Make sure that the tubing to the pump intake is fastened
securely so that it cannot come out of the pump intake
port. Check for local code requirements. You must com-
ply with codes.
3/8" ID Tubing
To Floor Drain
or Laundry Tub.
Do not kink tube!
1/2" Hose
Clamp
Run tubing as shown from hose barb on pump
3
discharge to floor drain or laundry tub.
Check local codes for discharge water requirements.
Run the discharge line to a point outside the house if
possible. To do this easily, you may be able to run the
condensate discharge line out through the wall along
the AC freon line. Use the existing line if possible (when
replacing an existing pump).
Clamping the plastic discharge line to the check valve
with a 1/2" hose clamp (purchase separately) will help
to keep it in place, especially with older tubing (plastic
tubing tends to harden as it gets older).
Common locations for the end of the discharge line are:
A. Out a window or along the air conditioner freon line
to the outdoors.
B. To a floor drain (leave an air gap between the end of
the tube and the drain).
C. To a laundry tub or sink (leave an air gap above the
tub drain).
1-800-468-7867 / 1-800-546-7867
3
Ceiling and Joists
Discharge tube should
slope down toward
outlet if possible
5492 0906

Publicité

Table des Matières
loading

Table des Matières