26
Approvals
Functional
Safety
Type
Approved
Further data
RoHS conformity
3)
MTBF
Ambient temperature
Ambient conditions
Housing
Diameter of the test jacks
Ingress protection
Mounting
Connection
Weight
1)
Average T c in specified operating temperature range
2)
For SIL applications, the 20 mA signal lines must be galvanically isolated from the mains.
3)
Mean Time Between Failures – according to EN 61709 (SN 29500)
Conditions: operation in well-kept rooms, average ambient temperature 40 °C,
no ventilation, continuous operation
4)
Closed, weather-protected operating areas,
water or wind-driven precipitation (rain, snow, hail, etc.) excluded
5)
Lower air pressure reduces the allowable working voltages.
Explosion protection
ATEX
UL (USA/Canada)
GL
2)
Functional safety
Suitable up to SIL 3 (see SIL safety manual, from page 27 onwards)
Suitable for PL c or PL e
(see SIL safety manual, from page 27 onwards)
According to directive 2011/65/EU
Average ambient
temperature
40 °C
60 °C
85 °C
During operation
During storage
Indoor use
4)
Relative humidity: 5 ... 95%, no condensation
Altitude up to 2000 m (air pressure: 790 ... 1060 hPa)
Design
Dimensions
2.1 mm
Housing and terminals
For 35-mm DIN rail acc. to EN 60715
Conductor cross section max. 2.5 mm
Tightening torque: 0.6 Nm
2 channels: approx. 90 g, 1 channel: approx. 60 g
Specifications
Zone 2 nA, IIC, T4 (functional separation)
II 3G Ex nA IIC T4 Gc X
cULus listed Open-type Process Control
Equipment also listed Proc. Contr. Eq. for
Use in Haz. Loc.
UL OrdLoc listed ANSI/UL 61010-1
UL HazLoc marking: Class I Div. 2 Groups
A,B,C,D T4
GL EMC 2 C
MTBF (approx.):
1106 years
639 years
274 years
-40 ... +85 °C (-40 ... 185 °F)
when mounted in row
-40 ... +85 °C (-40 ... 185 °F)
Modular housing with pluggable
screw terminals
99 x 114.5 x 12.5 mm (L x H x W)
IP 20
2
, AWG 20-12
5)