Electrical Connection; Cable Routing - Balluff BIP LD2-T017-01-EP-S4 Série Notice D'utilisation

Table des Matières

Publicité

BIP LD2-T017-01-EP _ _ / EP _ _ -S4
Inductive Positioning System
4
Installation and connection (continued)
4.2

Electrical connection

2
4
1
Fig. 4-4:
Pin assignment of S4 connector
(view from above on connector of BIP)
Connector/
Wire color
pin
1
Brown
2
3
Blue
4
Black
Unassigned leads that are not used can be connected to the GND on
1)
the controller side but not to the shield.
Tab. 4-1:
Pin assignments
4.3

Cable routing

Defined ground!
The BIP and the control cabinet must be at the
same ground potential.
Magnetic fields
The BIP operates according to the eddy current principle.
It is important to maintain adequate distance between the
BIP and strong, external magnetic fields.
Cable routing
Do not route the cable between the BIP, controller, and
power supply near high voltage cables (inductive stray noise
is possible).
Inductive stray noise from AC harmonics (e.g. from phase
angle controls) are especially critical and the cable shield
offers very little protection against this.
Cable length
Cable length max. 20 m. Longer cables may be used if
their construction, shielding and routing prevent noise
interference.
Bending radius for fixed cable
The bending radius for a fixed cable must be at least three
times the cable diameter.
8
english
Signal
L+ (18
30 V)
...
Not used
1)
L– (GND)
C/Q (communication line)

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Bip ld2-t017-01-ep série

Table des Matières