8.6

Display messages

Display message
Description
LOW BATTERY
The battery voltage has fallen
below the minimum value for
starting up (9V).
Check OIL Level
OIL CHANGE
The number of prescribed
operating hours has been
reached for changing the
engine oil.
NO FUEL
The diesel fuel in the tank is
in reserve.
PRESS OIL TEMP
Insufficient engine oil.
Engine temperature too high.
GENERATOR ALERT!
General alarm message
OVERLOAD!
The consumers generate an
overload at the output.
SHORT CIRCUIT
The consumers cause a short
circuit at the output.
EN
Generator behaviour
The generator does not start.
The generator continues to
run.
The generator continues to
run.
The generator continues to
run.
The generator stops.
The generator stops.
The inverter switches off,
therefore no voltage is sup-
plied but the engine carries
on running until it goes off.
The inverter switches off,
therefore no voltage is sup-
plied but the engine carries
on running until it goes off.
Operating the generator
Measures
Charge the battery.
Fill up with oil (see chapter
"Checking the oil level" on
page 19).
Change the oil (see chapter
"Changing the oil" on
page 23).
In order to reset the alarm
start up the generator by
pressing and holding down
the START/STOP button.
Refuel.
Fill up with oil (see chapter
"Checking the oil level" on
page 19).
Leave the generator to cool
down for a few minutes then
start up the generator again.
Check the system by referring
to the troubleshooting table.
If the problem persists, con-
tact the manufacturer's
branch office in your country
(addresses on the back
page).
Reduce the connected load
and start the generator again.
Check the connected con-
sumers then start the genera-
tor again.
17