The maintenance-free microprocessor-controlled duct sensor AERASGARD
without display, is used for detecting the CO
into standard signal of 0 -10 V.
The maintenance-free microprocessor-controlled duct sensor AERASGARD
switches), enclosure with quick-locking screws, optionally with / without display, is used for detecting the CO
0...2000 ppm or 0...5000 ppm. The measurement value is converted into standard signal of 0 -10 V or 4...20 mA.
The CO
content of the air is measured using an optical NDIR sensor (non-dispersive infra-red technology). The detection range of the CO
2
calibrated for standard applications such as monitoring residential rooms and conference rooms. Room ventilation on an as-needed basis, improved
well-being and customer benefit, increased comfort as well as reduced operating costs through energy conservation are just some of the benefits of
®
employing AERASGARD
CO
2
light source and a receptor. A certain range of wavelengths of light radiated by the source is damped and absorbed by CO
section. This damping is detected by the receptor.
TECHNICAL DATA
Power supply:
Power consumption:
Sensor:
Measuring range:
Output:
Relay output:
Measuring accuracy:
Temperature dependence:
Pressure dependence:
Long-term stability:
Gas exchange:
Warm up time:
Ambient temperature:
Response time:
Electrical connection:
Enclosure:
Enclosure dimensions:
Cable gland:
Protective tube:
Process connection:
Protection class:
Protection type:
Standards:
Optional:
- SD / KCO
-W
2
2
content of the air within a range of 0...2000 ppm or 0...5000 ppm. The measurement value is converted
2
sensors. A measuring system based on NDIR (non-dispersive infra-red technology) for CO
24 V AC ⁄ DC (± 10 %)
< 1.5 W ⁄ 24 V DC typical; < 2.9 VA ⁄ 24 V AC typical; Peak current 200 mA
optical NDIR sensor (non-dispersive infra-red technology)
with manual calibration (via zero button),
KCO
- SD with automatic calibration (fixed)
2
KCO
-W with automatic calibration (can be deactivated via DIP switches)
2
Multi-range switching (selectable via DIP switches)
0...2000 ppm; 0...5000 ppm
KCO
- SD 0 -10 V (fixed)
2
KCO
- W 0 -10 V or 4...20 mA, working resistance < 800 Ω (selectable via DIP switches)
2
with offset potentiometer (± 10 % of the measuring range)
KCO
- SD without changeover contact
2
KCO
- W with potential-free changeover contact (24 V / 1 A), switchpoint adjustable
2
± 30 ppm ± 3 % of measured value
± 5 ppm ⁄ °C or ± 0.5 % of measured value ⁄ °C (whichever is higher)
± 0.13 % ⁄ mm Hg
< 2 % in 15 years
by diffusion
approx. 1 hour
–10...+60 °C
approx. 1 minute
2
0.14 - 1.5 mm
, via screw terminals
plastic, UV-stabilised, material polyamide, 30 % glass-globe reinforced,
colour traffic white (similar to RAL 9016), enclosure cover for display is transparent!
KCO
- SD with snap-on lid
2
KCO
-W with quick-locking screws (slotted ⁄ Phillips head combination)
2
72 x 64 x 37.8 mm (Tyr 1/Tyr 01 without display)
72 x 64 x 43.3 mm (Tyr 1 with display)
M 16 x 1.5; including strain relief, exchangeable, max. inner diameter 10.4 mm
TM
PLEUROFORM
, material polyamide (PA6), with torsion protection,
Ø 20 mm, NL = 202.5 mm, v
via flange made of plastic (included in scope of delivery)
III (according to EN 60 730)
KCO
- SD IP 43 (as per EN 60 529) enclosure only !
2
KCO
- W IP 65 (as per EN 60 529) enclosure only !
2
CE conformity, electromagnetic compatibility according to EN 61 326, EMC Directive 2014 ⁄ 30 ⁄ EU
Display with illumination, two line, cutout approx. 36 x15 mm (W x H),
for displaying the Actual CO
®
KCO
- SD with automatic calibration (fixed), enclosure with snap-on lid,
2
®
KCO
- W with automatic calibration (can be deactivated via DIP
2
= 30 m/s (air)
max
content and for setting the switchpoint
2
Rev. 2018 - V37 GB
content of the air within a range of
2
sensor is
2
measurement consists of a
2
molecules in the measured
2