13.1. FLOOR MOUNTING
Figure 13.1.1. floor mounting
Figure 13.1.2. Darining
When AHU (1) is already placed the draining system has to be connected. In order to do that the thimble (or coupling)(2) must be screwed to the
AHU draining exhaust.
The system must be connected with pipe (4) in such order: AHU (1), siphon (3) and sewerage system (5). Pipe (4) should be bended not less than
3° degrees (1 meter of pipe must be bended 55 mm downwards)! Before turning on AHU (1) the draining system should be filled up with at least 0,5
l of water (siphon (3) must be always filled with water), also check if water reaches sewerage system (5)! In other case premises can be flooded.
Draining system must be installed in the premises where the temperature is not lower than 0°C. If temperature falls below 0°C the draining system
should be isolated with thermal isolation.
The siphon (3) must be mounted below the AHU's (1) level.
14. CONNECTION OF THE AIR DUCT
D2 dimensions depend on unit.
RIS 1200-2200 V EKO 3.0 v2019.05
FR |
9