ioControl
Transmit PDO mapping (index 0x1A00...0x1AFF):
Index
S-idx
Designation
0x1A00
0x00
Transmit
PDO map-
ping
Number of
mapped
objects in
PDO
0x01
PDO map-
ping
0x02
PDO map-
ping
0x03
PDO map-
ping
0x04
PDO map-
ping
0x05
PDO map-
ping
0x06
PDO map-
ping
0x07
PDO map-
ping
60
Data type
Default
rw
USINT
0x07
rw
UDINT
0x6000 0108
rw
UDINT
0x6000 0208
rw
UDINT
0x2020 0108
rw
UDINT
0x2020 0208
rw
UDINT
0x2021 0108
rw
UDINT
0x2021 0208
rw
UDINT
0x2025 0108
Details (CR2050)
mapping transmit PDO 1
number of integrated application
objects = 7
Index 0x6000, SubIndex 0x01
binary inputs 00���07: actual values
(bit coded)
Index 0x6000, SubIndex 0x02
binary inputs 08...15: actual values
(bit coded)
Index 0x2020, SubIndex 0x01
binary inputs 00���07: flag "short
circuit" (bit coded)
Index 0x2020, SubIndex 0x02
binary inputs 08...15: flag "short
circuit" (bit coded)
Index 0x2021, SubIndex 0x01
outputs 00���07: flag " wire break " (bit
coded)
Index 0x2021, SubIndex 0x02
outputs 08...15: flag " wire break "
(bit coded)
Index 0x2025, SubIndex 0x01
inputs 00���03: flag " overload " (bit
coded)