BG2I/BG2W:
The unit is operated by the breaking of the glass. The operator is protected from the broken glass by the vinyl
glass label.
Replacement of the glass:
To replace the glass after operation of the unit, remove the small cover held in place by the 2 slotted screws. Take
out the glass and remove any broken fragments from the unit. Place the new glass into the unit and replace the
cover, then test the unit as described below.
Testing the unit:
Using the test key provided, insert the key into the test hole (situated on bottom right hand side of the glass
cover) and engage into test cam. Turn the key in a clockwise direction (approx. 60°). This will simulate the
breaking of the glass. Release the key to reset the callpoint.
NOTE: MEDC DO NOT recommend forcing the test key further than 80° clockwise or 0° anti-clockwise as
this may lead to premature failure of the test cam.
4. MAINTENANCE
During the working life of the unit, it should require little or no maintenance. However, if abnormal or
unusual environmental conditions occur due to plant damage or accident etc., then visual inspection is
recommended.
If a unit fault should occur, then the unit can be repaired by MEDC. All parts of the unit are replaceable.
If you acquired a significant quantity of units, then it is recommended that spares are also made available. Please
discuss your requirements with the Technical Sales Engineers at MEDC.
09/17
© Eaton MEDC Ltd 2017