Regency Alterra CS1205 Guide D'installation Et D'utilisation page 48

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

installation
MINIMUM ALCOVE CLEARANCE TO COMBUSTIBLE MATERIALS
MEASUREMENTS "FROM UNIT" ARE FROM THE SIDE SHIELDS OF THE STOVE TO A SIDE WALL OR TO A CORNER, AND FROM
THE REAR HEAT SHIELD TO A BACK WALL
The Regency Freestanding models have been alcove approved and must be installed
with a listed double wall connector to the ceiling level.
Note: Minimum alcove ceiling height - 84"
Maximum depth of alcove - 36"
Minimum Alcove Clearance to Combustible Materials
Unit
CS1205
Floor Protection
A combustible floor must be protected by a non-combustible material (like tile,
concrete board, or certified to UL-1618 or as defined by local codes) extending
beneath the heater and a minimum of 6" from each side and minimum 16" from
the fuel door opening of the stove and minimum 6" (or the rear clearance to
combustibles whichever is smaller) from the rear of the stove.
Minimum Overall Width (X) of Floor
Protector for all installations:
US
38-3/4"
Canada
42-3/4"
NOTE: In Canada, floor protection must extend 18" to the front and 8" to each side of the stove.
Minimum Overall Depth (Y) of Floor Protector
Unit
CS1205
USA
Canada
8
|
Regency CS1205 Freestanding Wood Stove
From Back Shield
+ Side Shields.
G
H
11"
7"
Residential
"C" Vent
Close Clearance
Y
Z
39"
6"
43"
8"
From Flue
Center-Line
I
J
24-1/2"
14-1/2"
Z
6"
6"
X
6"
for
angled
corners
Residential
Mobile Home
Close Clearance
Z
Y
Y
39
6"
39"
43"
8"
43"
Min.
Min. Hearth
Width
to Rear Wall
K
49-1/8"
6"
X
Y
6"
16"
16"
Y
6"
Alcove
Z
Y
Z
6"
39"
6"
8"
43"
8"
L
39-1/4"
Z

Publicité

Chapitres

Table des Matières
loading

Table des Matières