MINIMUM CLEARANCE TO COMBUSTIBLE MATERIALS
MEASUREMENTS "FROM UNIT" ARE FROM THE SIDE SHIELDS OF THE STOVE TO A SIDE WALL OR TO A CORNER, AND FROM
THE REAR HEAT SHIELD TO A BACK WALL
NOTE: Be aware that local Codes and Regulations may override some clearances listed in this manual.
Check with your local inspector.
Residential Installation "C" Vent (Single Wall)
Unit
CS1205
Residential Close Clearance (To be installed with required pipe components)
When the stove is installed as a close clearance residential unit, a listed double wall connector is required from
the stove collar to the ceiling level.
CS1205
Mobile Home Close Clearance (To be installed with required pipe components)
"C" Vent single wall pipe is not approved for Mobile Home installations. (Refer to Mobile Home Instructions.)
CS1205
B
E
A
D
From Unit
A
B
13"
11"
From Unit
A
B
11"
7"
From Unit
A
B
11"
7"
F
C
From Corner
C
D
8"
26-3/8"
From Corner
C
D
7"
24-1/2"
From Corner
C
D
7"
24-1/2"
installation
F
C
From Flue Center-line
E
F
18-1/2"
20-3/4"
From Flue Center-line
E
F
14.5"
19-3/4"
From Flue Center-line
E
F
14.5"
19-3/4"
Regency CS1205 Freestanding Wood Stove
|
7