RFE1000 - CONNECTIONS FOR OPERATION
2. PARALLEL OPERATION
2.1. Remote sensing and current balance.
+V
RFE1000 #1
+S
-S
SIG.
ON/
-V
CS
CS
RTN
OFF
J1-7
J1-9
J1-11
J1-6
+V
RFE1000 #2
+S
-S
SIG.
ON/
CS
CS
RTN
OFF
-V
J1-7
J1-9
J1-11
J1-6
+V
RFE1000 #N
+S
-S
SIG.
ON/
-V
CS
CS
RTN
OFF
J1-7 J1-9
J1-11
J1-6
Up to 8 RFE1000 units of the same output voltage rating can be connected in parallel.
By connecting the CS signal between the paralleled units, automatic current balance is achieved,
with +/-10% accuracy.
Derate the total output current by 10% when using parallel operation to prevent overload condition.
The built-in Oring diodes on the main output and the 12V Auxiliary output allow N+1 operation.
For input voltages less than 100Vac, maximum output Power derated by 10% of the Power rating.
+S
-S
+S
+V
+S
-S
-V
-S
+S
-S
Fig 2-1
20