REAR IN/OUT CONNECTOR PINS FUNCTION DESCRIPTION
Pin No
Function
J1- 3
+V
J1- 10
-V
J1- 6
On/Off control
J1- 1
+Sense
J1- 5
DC_OK
J 1- 11
SignaLReturn
J1-12
AC_Fail
J1- 8
Over Temperature Alarm
J1- 2
-Sense
J1-7,9
CS
J1- 4
+12V Auxiliary
Pin No
Function
TB-1
AC Neutral
TB-2
AC Line
TB-3
AC Ground
Table 1: Rear In/Out connector pins function description
Refer to Table 1 for description of the control and supervisory signals provided at the rear In/Out connector. Refer to Fig. 1.1- 5.1 for typical connections
for operation.
Options
Suffix
RFE1000 -Y
Description
Positive output voltage
Negative output voltage
Turns the output to On and Off by electrical signal or dry contact between pin 6
and pin 11 (Signal Return). 0-0.6Vor Short: On, 2-15Vor Open: Off.
The maximum sink current is 2.6mA
Positive sensing. The +Sense signal should be connected to the positive terminal of the load.
The +Sense and -Sense leads should be twisted pair to minimize noise pick-up effect.
The maximum load wires drop compensation is 1V/wire.
Open collector signal, referenced to pin 11 (Signal Return). On when Vout ≥80%+/-5%
The maximum sink current is 10mA and the maximum external voltage is 15V.
Return for the following control and supervisory signals: On/Off, DC_OK,
Over_temperature Alarm, AC_Fail, Auxiliary 12V supply. The Signal return is isolated from the
output terminals.
Open collector signal, referenced to pin 11 (Signal Return). On when the input voltage is
≥85Vrms. The maximum sink current is 10mA and the maximum external voltage is 15Vdc.
Open collector signal, referenced to pin 11 (Signal Return). On when the internal temperature is
within safe limit, Off approx. 10°C below Thermal shut down.
The maximum sink current is 10mA and the maximum external voltage is 15V.
Negative sensing. The -S signal should be connected to the negative terminal of the load.
The -S and +S leads should be twisted pair to minimize noise pick-up effect.
The maximum load wires drop compensation is 1 V/wire.
Current sharing signal. When units are connected in parallel, the CS pins of the
units should be connected to allow current balance between units.
Auxiliary voltage output, 11.2-12.5V. referenced to pin 11 (Signal Return).
The maximum load current is 0.25A. This output has built in Oring diode and is not controlled by
the On/Off control.
Descriotion
AC Neutral connection. Refer to the safety instructions for safety standards requirements.
AC Line connection. Refer to the safety instructions for safety standards requirements.
AC Ground connection. Refer to the safety instructions for safety standards requirements.
Description
O Ring output diode
14