If MODE CPs
4
% on K3?
5
INIT CPs REF?
6
m³h INIT
7
CPs INIT
x,xx V
xxxx m³h
xxxx Pa
8
END SETUP
5) What you can see on the screen
5.1 Basic display
The default setting displays actual airflow, pressure and alarm (if activated).
More information available on the PLC website :
5.2 Display all the parameters
↑
By pressing knobs
and
More information available on the PLC website :
6) Fan running status
One of 2 relays of the SAT3 option indicates if the fan is actually running (actual value > 20% requested value) or not.
This allows for example to start an electrical heating coil or a compressor only when the fan is actually running (contact
closed). It is an extra safety feature because you have the cetainty the fan is actually running (closed loop principle)
Wiring diagram: see appendix §
Select multiplier for CPs resulting airflow when terminals +12V and K3 are closed ('night'
setup).
Setup of CPs fan pressure instruction ?
If you have selected Y: Enter nominal airflow to determine corresponding pressure CPs.
Initialisation of the reference pressure busy. After 1 minute the CB will memorize the value
of the measured static pressure once the INIT airflow is reached.
Display of instant value of airflow, pressure and sensor value while initializing .
Configuration is finished.
↓
you can activate display the status of all the parameters :
.
.
2
www.swegon.com
www.swegon.com