4-14. Auxiliary Supply
Auxiliary supply (5V, 0.3A max) is provided to ease customer application. Aux voltage is always available as long as
input power in the specified voltage range is present.
4-15. Output Dynamic Load Response
During output dynamic load test from no load condition, the output voltage level might experience a higher voltage dip
of 15% (typ).
For example, VIN = 230VAC Dynamic Load = 0% - 100% Ta = 25degC, the output voltage level dip will be -15% (typ).
5. Isolation / Withstand Voltage
5-1. Isolation Test
Isolation resistance between output and FG (chassis) shall be more than 100M at 500VDC. For safety, voltage setting
of DC isolation tester must be done before the test. Ensure that the unit is fully discharged after the test.
(a) Output ~ FG (chassis) : 500VDC, 100M or more