5. WIRING
Power supply and connecting wires specification
Model
Phase
Frequency and volt
Indoor
Rated Current
Fuse Rating(Field Supply)
Power Cord(Field Supply)
Phase
Frequency and volt
Outdoor
Rated Current
Circuit Breaker(Field Supply)
Power Cord(Field Supply)
Indoor/outdoor connecting wiring
(Field Supply)
Connection Diagram
Indoor Unit (QZL036~060)
L
N
X
Power Input To Outdoor
CAUTION
Separate the low voltage wiring (signal wire) and high voltage wiring (power supply wiring) at least 0.5m so that they do not
pass through the same place together. Proximity may cause electrical interference, malfunctions, and breakage.
GB-16
QUS036
1-Phase
220-240V~ 50Hz
1.8A
16A
H05VV-F; 3×1.0mm
1-Phase
220-240V~ 50Hz
21.0A
40A
H07RN-F; 3×4.0mm
Shielded cable; 2×0.2mm
Y (E)
S1 S2
QUS048
1-Phase
220-240V~ 50Hz
1.0A
16A
2
H05VV-F; 3×1.0mm
3-Phase
380-415V 3N~ 50Hz
13.0A
30A
2
H07RN-F; 5×2.5mm
2
Shielded cable; 2×0.2mm
Outdoor Unit (QUS036)
L
N
S1
S2
Power Input To Indoor
Outdoor Unit (QUS048~60)
L1
L2
L3
N
S1
Power Input To Indoor
QUS060
1-Phase
220-240V~ 50Hz
1.5A
16A
2
H05VV-F; 3×1.0mm
2
3-Phase
380-415V 3N~ 50Hz
13.0A
30A
2
2
H07RN-F; 5×2.5mm
2
Shielded cable; 2×0.2mm
Power input cord
(Single phase)
60mm
GND
10mm
40mm
Power input cord
(Three phase)
GND
60mm
10mm
40mm
S2
2