Make sure to save this manual for future reference. Please check the applicable models, F-GAS and manufacturer information from the “Owner's Manual - Product Fiche” in the packaging of the outdoor unit. (European Union products only) For German/Dutch/Poland/Denmark/Estonia/Lithuania/Latvia/Norway/Sweden/ Portugees languages, please visit the website: www.beijerref-carrier.com...
CONTENTS 1. PREPARING FOR INSTALLATION ······································································ Safety Percautions ························································································· Accessories ·································································································· 2. INDOOR UNIT INSTALLATION ··········································································· Installation Site Choosing ················································································ Install The Indoor Unit ···················································································· How To Connect The Pipes And Wires ······························································· Install The Drain Pipe ····················································································· 3. OUTDOOR UNIT INSTALLATION ······································································...
1. PREPARING FOR INSTALLATION 1.1 SAFETY PRECAUTIONS Installing, starting up, and servicing air-conditioning equipment can be hazardous due to system ressures, electrical components, and equipment location (roofs, elevated structures, etc.). Only trained, qualified installers and service mechanics should install, start-up, and serve this equipment. When working on the equipment, observe precautions in the literature and on tags, stickers, and labels attached to the equipment.
Page 5
1. PREPARING FOR INSTALLATION WARNING In order to avoid a hazard due to inadvertent resetting of the thermal cut-out, this appliance must not be supplied through an external switching device, such as a timer, or connected to a circuit that is regularly switched on and off by the utility.
1. PREPARING FOR INSTALLATION CAUTION This symbol indicates the possibility of property damage or serious consequences. Perform the drainage/piping work securely according to the installation manual. Improper drain piping may result in water leakage and property damage. Do not instal the air conditioner in the following places. -The place where there is mineral oil or arsenic acid.
2. INDOOR UNIT INSTALLATION 2.1 INSTALLATION SITE CHOOSING INDOOR UNIT ■ Where it is out of direct sunlight. ■ Where the airflow is not blocked. ■ Where an optimum air distribution is ensured. ■ Where the condensate can drain correctly and safely. ■...
2. INDOOR UNIT INSTALLATION 2.2 INSTALL THE INDOOR UNIT 2.2.1 Fix the hook with tapping screw onto the wall. Hook Tapping screw Washer <6mm 2.2.1 Hang the indoor unit on the hook. CAUTION The unit must be installed vertically. There should be no gap between unit and the ground.
2. INDOOR UNIT INSTALLATION 2.3.3 Remove 4 screws, and then remove the frame from bottom side. Piping connection port and drain hose connection port can be observed after take off the frame. Piping connection port Drain hose connection port 2.3.4 Remove the installation bearer, and take off control box cover. Wiring terminator can be observed.
3. OUTDOOR UNIT INSTALLATION 3.3 SPACE REQUIREMENT FOR OUTDOOR UNIT Single Unit Installation (Wall or obstacle) Air inlet >30cm Maintain channel Air inlet Fix with bolt >60cm Air outlet unit:cm Parallel connect the front with rear sides. unit:cm Parallel connect the two units or above >200 >50 >300...
4. REFRIGERANT PIPING WORK CAUTION Check if the height difference between indoor unit & outdoor unit and the total length of refrigerant pipe meet system requirement. Refrigerant piping work follows the indoor unit and outdoor unit installation, connect the pipe at the indoor side first, then the outdoor side.
6. FINAL CHECK AND TRIAL OPERATION 6.1 FINAL CHECK LIST To complete the installation, perform the following checks before the trial operation. Strength of the installation site for both indoor and outdoor sides, confirm no obstruction of the unit air outlet or return.
7. INFORMATION SERVICING 7.1 CHECKS TO THE AREA Prior to beginning work on systems containing flammable refrigerants, safety checks are necessary to ensure that the risk of ignition is minimised. For repair to the refrigerating system, the following precautions shall be complied with prior to conducting work on the system.
Page 17
7. INFORMATION SERVICING the charge size is in accordance with the room size within which the refrigerant containing parts are installed; the ventilation machinery and outlets are operating adequately and are not obstructed; if an indirect refrigerating circuit is being used, the secondary circuits shall be checked for the presence of refrigerant;...
Page 18
7. INFORMATION SERVICING 7.12 CABLING Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration, sharp edges or any other adverse environmental effects. The check shall also take into account the effects of aging or continual vibration from sources such as compressors or fans.
Page 19
7. INFORMATION SERVICING 7.16 CHARGING PROCEDURES In addition to conventional charging procedures, the following requirements shall be followed: Ensure that contamination of different refrigerants does not occur when using charging equipment. Hoses or lines shall be as short as possible to minimize the amount of refrigerant contained in them. Cylinders shall be kept upright.
Page 20
7. INFORMATION SERVICING 7.19 RECOVERY When removing refrigerant from a system, either for service or decommissioning, it is recommended good practice that all refrigerants are removed safely. When tranferring refrigerant into cylinders, ensure that only appropriate refrigerant recovery cylinders are employed.
Page 23
CONTENIDO 1. PREPARACIÓN DE LA INSTALACIÓN ................3 ....................3 1.1 Precauciones de seguridad ......................... 4 1.2 Accesorios 2. INSTALACIÓN DE LA UNIDAD INTERIOR ................. 6 ..................6 2.1 Elección del lugar de instalación ................... 7 2.2 Instalación de la unidad exterior ................
1. PREPARACIÓN DE LA INSTALACIÓN 1.1 PRECAUCIONES DE SEGURIDAD La instalación, puesta en marcha y mantenimiento de equipos de aire acondicionado puede ser peligrosa debido a las presiones del sistema, componentes eléctricos y ubicación de los equipos (techos, estructuras elevadas, etc.). La instalación, puesta en marcha y mantenimiento de este equipo solo debe ser realizada por instaladores y mecánicos de mantenimiento cualificados y con la debida formación.
Page 25
1. PREPARACIÓN DE LA INSTALACIÓN ADVERTENCIA Con el fin de evitar situaciones de peligro debido al reseteado accidental de la protección térmica, la alimentación eléctrica de este aparato no debe realizarse a través de un dispositivo de conmutación externo, como por ejemplo un temporizador, ni debe ir conectado a un circuito que la compañía eléctrica enciende y apaga regularmente.
1. PREPARACIÓN DE LA INSTALACIÓN PRECAUCIÓN Este símbolo indica la posibilidad de daños a la propiedad o consecuencias graves. Para evitar lesiones personales, tenga cuidado al manejar piezas con bordes afilados. No instale las unidades interior o exterior en un lugar con condiciones ambientales especiales. No debe instalarse en un lugar que pueda amplificar el nivel de ruido de la unidad o donde el ruido y aire descargado pueda molestar a los vecinos.
2. INSTALACIÓN DE LA UNIDAD INTERIOR 2.1 ELECCIÓN DEL LUGAR DE INSTALACIÓN UNIDAD INTERIOR ■ Donde esté fuera de la luz solar directa. ■ Donde el caudal de aire no esté bloqueado. ■ Donde se garantice una óptima distribución de aire. ■...
2. INSTALACIÓN DE LA UNIDAD INTERIOR 2.2 INSTALE LA UNIDAD INTERIOR 2.2.1 Fije el gancho con el tornillo roscado en la pared. Gancho Tornillo roscado Arandela <6mm 2.2.1 Cuelgue la unidad interior en el gancho. PRECAUCIÓN La unidad debe instalarse verticalmente. No debe haber ningún hueco entre la unidad y el suelo.
2. INSTALACIÓN DE LA UNIDAD INTERIOR 2.3.3 Saque los 4 tornillos y, a continuación, extraiga el marco del lado inferior. La boca de conexión de tuberías y la boca de conexión de la manguera de desagüe se pueden observar después de quitar el marco.
3. INSTALACIÓN DE LA UNIDAD EXTERIOR 3.3 REQUISITO DE ESPACIO PARA LA UNIDAD EXTERIOR Instalación de la unidad individual (Pared u obstáculo) Entrada de aire >30cm Mantener canal Entrada Fijar con tornillo de aire >60cm Salida de aire Conecte en paralelo las dos unidades o por encima Conexión en paralelo de los lados delanteros y traseros.
4. TUBERÍAS DE REFRIGERANTE PRECAUCIÓN ■ Compruebe si la diferencia de altura entre la unidad interior y exterior y la longitud total de la tubería refrigerante satisface los requisitos del sistema. ■ Las tuberías de refrigeración siguen la instalación de la unidad interior y exterior, conectando primero la tubería del lado interior y luego las del lado exterior.
6. COMPROBACIÓN FINAL Y FUNCIONAMIENTO PILOTO 6.1 LISTA DE COMPROBACIÓN FINAL Para completar la instalación, realice las siguientes comprobaciones antes del funcionamiento piloto. ■ Resistencia del lugar de la instalación tanto por el lado interior como exterior, confirme que no haya obstrucción de la salida de aire de la unidad ni devolución. ■ Tensión de la conexión de tuberías refrigerantes y confirmación de que no hay fugas ■ Las conexiones de cableado eléctrico están perfectamente acabadas y la unidad se ha conectado a tierra ■...
7. INFORMACIÓN PARA EL SERVICIO TÉCNICO 7.1 COMPROBACIONES EN EL ÁREA Antes de comenzar a trabajar en sistemas que contienen refrigerantes inflamables, hay que realizar comprobaciones de seguridad para garantizar que el riesgo de ignición se reduce al mínimo. En la reparación del sistema de refrigeración, hay que cumplir las siguientes precauciones antes de realizar trabajos en el sistema.
Page 37
7. INFORMACIÓN PARA EL SERVICIO TÉCNICO el tamaño de la carga debe ser adecuado para el tamaño de la sala en la que están instalados los componentes que contienen refrigerante; la maquinaria de ventilación y las salidas funcionan adecuadamente y no están obstruidas; si se utiliza un circuito de refrigeración indirecta, hay que verificar si en los circuitos secundarios se detecta presencia de refrigerante;...
Page 38
7. INFORMACIÓN PARA EL SERVICIO TÉCNICO 7.12 CABLES Verifique que los cables no estén sujetos a desgaste, corrosión, presión excesiva, vibración, bordes afilados o cualquier otro efecto ambiental adversos. La comprobación también deberá tener en cuenta los efectos del envejecimiento o la vibración continua de fuentes tales como compresores o ventiladores. 7.13 DETECCIÓN DE REFRIGERANTES INFLAMABLES En ningún caso se pueden utilizar fuentes potenciales de ignición para buscar o detectar fugas de refrigerante.
Page 39
7. INFORMACIÓN PARA EL SERVICIO TÉCNICO 7.16 PROCEDIMIENTOS DE CARGA Además de los procedimientos convencionales de carga, se deberán seguir las siguientes normas: Asegúrese de que no se contaminan los distintos refrigerantes al utilizar el equipo de carga. Las mangueras o tubos deberán ser lo más cortos que sea posible para reducir al mínimo la cantidad de refrigerante contenido en ellos.
Page 40
7. INFORMACIÓN PARA EL SERVICIO TÉCNICO 7.19 RECUPERACIÓN Al retirar el refrigerante de un sistema, ya sea para desmantelarlo o para repararlo, se recomienda encarecidamente que los refrigerantes se extraigan de forma segura. Al transferir el refrigerante a los cilindros, asegúrese de que solo se emplean cilindros de recuperación adecuados para el refrigerante. Asegúrese de que dispone de cilindros suficientes para la carga total del sistema.
Page 43
TABLE DES MATIÈRES 1. PRÉPARATION DE L'INSTALLATION .................. 3 ......................3 1.1 Consignes de sécurité ......................... 4 1.2 Accessoires 2. INSTALLATION DE L'UNITÉ INTÉRIEURE ................6 ..................6 2.1 Choix de l'emplacement d'installation ....................7 2.2 Installation de l'unité intérieure .................7 2.3 Raccordement des tuyaux et des câbles ..................
1. PRÉPARATION DE L'INSTALLATION 1.1 CONSIGNES DE SÉCURITÉ L'installation, la mise en service et l'entretien des équipements de climatisation peuvent s'avérer dangereux en raison de la pression du système, des composants électriques et de l'emplacement des équipements (toits, structures surélevées, etc.). Seul un installateur ou un technicien qualifié et formé doit installer, démarrer et entretenir cet équipement. vous utilisez cet équipement, respectez les précautions mentionnées dans la documentation et sur les étiquettes Lorsque et autocollants apposés dessus.
Page 45
1. PRÉPARATION DE L'INSTALLATION AVERTISSEMENT Pour éviter tout risque dû à la réinitialisation accidentelle du coupe-circuit thermique, cet appareil ne doit pas être alimenté par un dispositif de commutation externe, comme un temporisateur, ni connecté à un circuit qui est régulièrement activé et désactivé par le service fournisseur. Utilisez les câbles prescrits pour le raccordement électrique et protégez-les à...
1. PRÉPARATION DE L'INSTALLATION ATTENTION Ce symbole indique un risque de dommages matériels ou de conséquences graves. Pour éviter de vous blesser, soyez prudent lorsque vous manipulez des pièces avec des arêtes vives. N'installez pas les unités intérieures ou extérieures dans des conditions environnementales spéciales. N'installez pas l'appareil dans un endroit susceptible d'amplifier son niveau sonore ou dans lequel le bruit ou l'évacuation de l'air peuvent représenter une nuisance pour votre voisinage.
2. INSTALLATION DE L'UNITÉ INTÉRIEURE 2.1 CHOIX DE L'EMPLACEMENT D'INSTALLATION UNITÉ INTÉRIEURE ■ L'appareil doit être à l'abri de la lumière directe du soleil. ■ Le flux d'air ne doit pas être bloqué. ■ La distribution de l'air doit être optimale. ■ Les condensats doivent pouvoir être évacués correctement et en toute sécurité. ■ L'unité intérieure doit être installée sur un mur/plafond exempt de vibrations et assez résistant pour supporter le poids de l'appareil.
2. INSTALLATION DE L'UNITÉ INTÉRIEURE 2.2 INSTALLATION DE L'UNITÉ INTÉRIEURE 2.2.1 Fixez l'accroche sur le mur avec la vis taraudeuse. Accroche taraudeuse Rondelle <6 mm 2.2.1 Suspendez l'unité intérieure à l'accroche. ATTENTION L'appareil doit être installé à la verticale. Il ne doit y avoir aucun espace entre l'appareil et le sol.
2. INSTALLATION DE L'UNITÉ INTÉRIEURE 2.3.3 Retirez les 4 vis, puis le cadre de la partie inférieure. Les ports de raccordement de tuyauterie et de tuyau de vidange sont visibles une fois que le cadre a été enlevé. Port de raccordement de tuyauterie Port de raccordement de tuyau de vidange 2.3.4 Retirez le support d'installation, puis enlevez le couvercle de la boîte de commande.
3. INSTALLATION DE L'UNITÉ EXTÉRIEURE 3.3 ESPACE REQUIS POUR L'UNITÉ EXTÉRIEURE Installation d'une seule unité (Mur ou obstacle) Entrée d'air >30cm Canal à maintenir Entrée Fixer avec un boulon d'air >60 cm Sortie d'air Raccordement parallèle de deux unités ou plus Raccordez les côtés avant et arrière en parallèle. unité : cm unité : cm >...
4. TRAVAUX DE TUYAUTERIE POUR LE PRODUIT FRIGORIGÈNE ATTENTION ■ Vérifiez si la différence de hauteur entre l'unité intérieure et l'unité extérieure et la longueur totale du tuyau de produit frigorigène répondent aux exigences du système. ■ Les travaux de tuyauterie pour le produit frigorigène suivent l'installation des unités intérieure et extérieure. Raccordez le tuyau côté intérieur d'abord, puis côté extérieur. ■ Gardez toujours les extrémités des tuyaux scellées en plaçant un bouchon ou en les obstruant avec du ruban adhésif durant l'installation et ne les libérez QUE lorsque vous êtes prêt à les raccorder. ■ Veillez à isoler tout tuyau extérieur, tout le long jusqu'au raccordement à l'intérieur de l'appareil. Tout tuyau apparent peut provoquer de la condensation ou des brûlures en cas de contact. 4.1 ÉVASEMENT 4.2 TRAVAUX DE TUYAUTERIE REMARQUE...
6. VÉRIFICATION FINALE ET TEST DE FONCTIONNEMENT 6.1 LISTE DE VÉRIFICATION FINALE Pour terminer l'installation, effectuez les vérifications suivantes avant le test de fonctionnement. ■ Solidité de l'emplacement d'installation pour les deux unités, intérieure et extérieure. Non-obstruction de la sortie ou du retour d'air de l'unité. ■ Étanchéité des raccords de tuyauterie de produit frigorigène et absence de fuite ■ Raccordements électriques correctement effectués et mise à la terre de l'appareil ■...
7. INFORMATIONS RELATIVES À L'ENTRETIEN 7.1 VÉRIFICATIONS DANS LA ZONE Avant toute intervention sur des systèmes contenant des produits frigorigènes inflammables, des contrôles de sécurité sont nécessaires afin de s'assurer que le risque d'inflammation est réduit au minimum. En cas de réparation du système de climatisation, les précautions suivantes doivent être prises avant toute intervention. 7.2 PROCÉDURE DE TRAVAIL Les travaux doivent être entrepris dans le cadre d'une procédure contrôlée visant à réduire le risque de présence d'un gaz ou de vapeur inflammable pendant ces travaux. 7.3 ZONE DE TRAVAIL GLOBALE L'ensemble du personnel de maintenance et plus généralement les personnes qui travaillent dans la zone doivent être au courant de la nature du travail entrepris. Tout travail dans un espace confiné doit être proscrit. La zone qui entoure l'espace de travail doit être cloisonnée. Assurez-vous de la sûreté des conditions au sein de la zone grâce au contrôle des matières inflammables.
7. INFORMATIONS RELATIVES À L'ENTRETIEN la taille de la charge est adaptée à la taille de la pièce dans laquelle les parties contenant le produit frigorigène sont installées ; les appareils de ventilation et les orifices fonctionnent correctement et ne sont pas obstrués ; si un circuit de frigorigène indirect est utilisé, la présence de produit frigorigène doit être vérifiée dans les circuits secondaires ; le marquage de l'équipement doit être visible et lisible ; le marquage et les signes illisibles doivent être corrigés ; les tuyaux ou les composants de climatisation sont installés dans un endroit où ils ne sont pas susceptibles d'être exposés à des substances susceptibles corroder les composants contenant le produit frigorigène, sauf si ces composants sont fabriqués dans des matériaux intrinsèquement résistants à la corrosion ou sont correctement protégés contre une telle corrosion.
7. INFORMATIONS RELATIVES À L'ENTRETIEN 7.12 CÂBLAGE Vérifiez que le câblage n'est pas soumis à l'usure, à la corrosion, à une pression excessive ou à des vibrations, qu'il n'est pas en contact avec des arêtes vives ou qu'il n'est pas soumis à tout autre effet environnemental nuisible. La vérification doit également tenir compte des effets du vieillissement ou des vibrations continues provenant de sources telles que des compresseurs ou des ventilateurs. 7.13 DÉTECTION DES PRODUITS FRIGORIGÈNES INFLAMMABLES Des sources potentielles d'inflammation ne doivent en aucun cas être utilisées pour rechercher ou détecter des fuites de produits frigorigènes. Une lampe haloïde (ou tout autre détecteur utilisant une flamme nue) ne...
7. INFORMATIONS RELATIVES À L'ENTRETIEN 7.16 PROCÉDURES DE CHARGEMENT Outre les procédures conventionnelles de chargement, les exigences suivantes doivent être respectées : Assurez-vous que les différents produits frigorigènes ne sont exposés à aucune contamination lorsque vous utilisez un équipement de chargement. Les flexibles ou les conduites doivent être les plus courts possible, afin de réduire la quantité de produit frigorigène qu'ils contiennent. Les cylindres doivent être maintenus en position verticale. Assurez-vous que le système de climatisation est mis à la terre avant de le charger avec du produit frigorigène. Étiquetez le système lorsque le chargement est terminé (si ce n'est pas déjà fait). Des précautions extrêmes doivent être prises pour ne pas remplir le système de climatisation de façon excessive. Avant de recharger le système, sa pression doit être testée à l'azote libre d'oxygène. Le système doit être soumis à un test de fuites, après la fin du chargement, mais avant sa mise en service. Un test de suivi des fuites 7.17 DÉMANTÈLEMENT Avant d'entreprendre cette procédure, il est essentiel que le technicien ait une connaissance parfaite de...
7. INFORMATIONS RELATIVES À L'ENTRETIEN 7.19 RÉCUPÉRATION Lorsque vous retirez le produit frigorigène d'un système, que ce soit pour des opérations d'entretien ou pour son démantèlement, la bonne pratique recommandée est que les produits frigorigènes soient récupérés en totalité et de façon sécurisée. Lorsque vous transférez des produits frigorigènes dans des cylindres, assurez-vous de n'employer que des cylindres de récupération de produits frigorigènes appropriés. Assurez-vous de disposer d'un nombre correct de cylindres, capables de contenir l'ensemble de la charge du système. Tous les cylindres devant être utilisés sont conçus pour le produit frigorigène récupéré et sont étiquetés pour indiquer ce dernier (c.- à-d. cylindres spéciaux pour la récupération du produit frigorigène). Les cylindres doivent être dotés d'une soupape de sûreté et des robinets d'arrêt associés doivent être en bon état de marche. Les cylindres de récupération vides sont évacués et, si possible, refroidis avant la récupération. L'équipement de récupération doit être en bon état de marche.
Page 63
INDICE 1. PREPARAZIONE ALL'INSTALLAZIONE ................3 1.1 Precauzioni di sicurezza ......................... 3 1.2 Accessori ..............................4 2. INSTALLAZIONE DELL'UNITÀ INTERNA ................6 2.1 Scelta della posizione di installazione ....................6 2.2 Installazione dell'unità interna ......................... 7 2.3 Collegamento dei tubi e dei cavi ......................7 2.4 Installazione del tubo di scarico ......................
1. PREPARAZIONE ALL'INSTALLAZIONE 1.1 PRECAUZIONI DI SICUREZZA L'installazione, l'avviamento e la manutenzione dell'impianto di aria condizionata possono essere pericolosi a causa delle pressioni al sistema, dei componenti elettrici e dell'ubicazione dell'attrezzatura (tetti, strutture elevate, ecc.). Questa attrezzatura può essere installata, avviata e sottoposta a manutenzione solo da installatori e addetti alla manutenzione qualificati.
Page 65
1. PREPARAZIONE ALL'INSTALLAZIONE AVVERTENZA Per evitare il rischio dovuto alla reimpostazione involontaria dell'interruttore termico, questa attrezzatura non deve essere alimentata attraverso un dispositivo di commutazione esterno, come un timer, oppure collegata a un circuito che viene regolarmente acceso e spento mediante il dispositivo. Utilizzare i cavi prescritti per il collegamento elettrico con un isolamento protetto da una guaina di isolamento dotata dei valori di temperatura appropriati.
1. PREPARAZIONE ALL'INSTALLAZIONE ATTENZIONE Questo simbolo indica la possibilità di danni alle cose o di gravi conseguenze. Per evitare lesioni personali, prestare attenzione quando si maneggiano componenti con bordi affilati. Non installare le unità interne o esterne in punti con condizioni ambientali particolari. Non installare in un luogo che possa amplificare il livello di rumorosità...
2. INSTALLAZIONE DELL'UNITÀ INTERNA 2.1 SCELTA DELLA POSIZIONE DI INSTALLAZIONE UNITÀ INTERNA ■ Scegliere una posizione non esposta alla luce diretta del sole. ■ Scegliere una posizione in cui il flusso di aria non sia bloccato. ■ Scegliere una posizione in cui sia garantita una distribuzione dell'aria ottimale. ■ Scegliere una posizione in cui la condensa possa essere scaricata correttamente e in sicurezza. ■...
2. INSTALLAZIONE DELL'UNITÀ INTERNA 2.2 INSTALLAZIONE DELL'UNITÀ INTERNA 2.2.1 Fissare il gancio con la vite autofilettante sulla parete. Gancio Vite autofilet- tante Rondella <6mm 2.2.1 Fissare l'unità interna al gancio. ATTENZIONE L'unità deve essere installata verticalmente. Non deve esserci gioco tra l'unità e il suolo. Nessun gioco tra unità...
2. INSTALLAZIONE DELL'UNITÀ INTERNA 2.3.3 Rimuovere le 4 viti, quindi rimuovere il telaio dal lato inferiore. È possibile vedere la luce di collegamento del tubo e la luce di collegamento del tubo di scarico dopo aver rimosso il telaio. Luce di collegamento del tubo Luce di collegamento del tubo di scarico 2.3.4 Rimuovere il supporto di installazione ed estrarre il coperchio della scatola comandi.
3. INSTALLAZIONE DELL'UNITÀ ESTERNA 3.3 SPAZIO NECESSARIO PER L'UNITÀ ESTERNA Installazione dell'unità singola (Parete o ostacolo) Ingresso aria >30cm Canale per manutenzione Ingresso Fissare con il bullone aria >60cm Uscita aria Collegare le unità in parallelo Collegare le unità accoppiando unità...
4. INTERVENTO SUL TUBO DEL REFRIGERANTE ATTENZIONE ■ Controllare se la differenza di altezza tra l'unità interna e l'unità esterna e la lunghezza totale del tubo del refrigerante sono conformi alle specifiche. ■ Gli interventi sul tubo del refrigerante sono conformi all'installazione dell'unità interna e dell'unità esterna. Collegare il tubo prima sul lato interno, quindi sul lato esterno.
6. CONTROLLO FINALE E FUNZIONAMENTO DI PROVA 6.1 ELENCO DEI CONTROLLI FINALI Per completare l'installazione, effettuare i seguenti controlli prima del funzionamento di prova. ■ Verificare la resistenza del punto di installazione sia per il lato interno sia per il lato esterno e controllare che non ci siano ostruzioni nell'uscita o nel ritorno dell'aria dell'unità. ■ Verificare la tenuta del collegamento delle tubazioni del refrigerante e controllare che non ci siano perdite. ■ Verificare che i collegamenti elettrici siano stati completati correttamente e che sia stata predisposta una messa a terra dell'unità. ■...
7. INFORMAZIONI SULLA MANUTENZIONE 7.1 CONTROLLI SULL'AREA Prima di iniziare a lavorare su sistemi che contengono refrigeranti infiammabili, sono necessari controlli di sicurezza per ridurre al minimo i rischi di incendio. Prendere le seguenti precauzioni prima di effettuare interventi di riparazione sull'impianto. 7.2 PROCEDURA DI LAVORO I lavori devono essere controllati al fine di ridurre al minimo il rischio di presenza di gas infiammabili o vapore mentre viene effettuato l'intervento. 7.3 INFORMAZIONI GENERALI SULL'AREA DI LAVORO Tutto il personale addetto alla manutenzione deve essere informato della natura del lavoro effettuato.
Page 77
7. INFORMAZIONI SULLA MANUTENZIONE le dimensioni di ricarica devono basarsi sulle dimensioni della stanza in cui i componenti che contengono refrigerante vengono installati; i macchinari e le prese di ventilazione devono funzionare in modo adeguato e non essere ostruiti; se viene utilizzato un circuito refrigerante indiretto, i circuiti secondari devono essere controllati per la presenza di refrigerante;...
Page 78
7. INFORMAZIONI SULLA MANUTENZIONE 7.12 CABLAGGIO Controllare che il cablaggio non sia soggetto ad usura, corrosione, pressione eccessiva, vibrazioni, spigoli vivi o altri agenti ambientali avversi. Il controllo deve inoltre tener conto degli effetti dell'invecchiamento o delle vibrazioni continue da fonti come compressori o ventilatori. 7.13 RILEVAMENTO DI REFRIGERANTI INFIAMMABILI In nessun caso devono essere utilizzate potenziali fonti di accensione nella ricerca o nella rilevazione di perdite di refrigerante. Non utilizzare una torcia ad alogenuro (o qualsiasi altro rivelatore che utilizzi una fiamma libera).
Page 79
7. INFORMAZIONI SULLA MANUTENZIONE 7.16 PROCEDURE DI RICARICA Oltre alle procedure di ricarica convenzionali, devono essere soddisfatti i seguenti requisiti: Assicurarsi che non si verifichi la contaminazione di diversi refrigeranti quando si utilizzano apparecchiature di ricarica. I tubi flessibili o rigidi devono essere il più corti possibili per ridurre al minimo la quantità...
Page 80
7. INFORMAZIONI SULLA MANUTENZIONE 7.19 RECUPERO Quando si rimuove il refrigerante da un impianto, per la manutenzione o lo smantellamento, si raccomanda come buona pratica di rimuovere tutti i refrigeranti in sicurezza. Quando si trasferisce il refrigerante nelle bombole, garantire che vengano utilizzate solo bombole di recupero del refrigerante adeguate.