Lamborghini Caloreclima EM 16/2-E Notice D'installation Et D'entretien page 35

Masquer les pouces Voir aussi pour EM 16/2-E:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

EM 26/2-E
The connections to be carried out by the installer are:
- Main supply line
- Thermostatic line
- Lock-out lamp at terminal S3 (if present)
- Hour counter at terminal B4 (if present)
- Second stage hour counter at terminal 2 of 3-pole plug (if present)
- Flame modulation thermostat at terminals 1-3 of 3-pole plug (if present) (remove the bridge)
EC
Control electrode
F
Fuse
FA
Anti-interference filter
IG
Main switch
Ima ON/OFF switch
LI
Switch light
MB Burner motor
MS
Servocontrol terminal
board
NOTE: Always make sure that no more than two wires are connected to each terminal.
Warning:
- Do not invert the neutral with the phase
- Make the connection to an efficient earthing system
- The electrical power line to the burner must be fitted with an omnipolar switch with an ope-
ning of at least 3 mm between the contacts
- Must be workmanlike performed and comply with the regulations in force.
MPE Control box terminal board
MV
Detachable terminal
PA
Air pressure switch
PGm Minimum gas
pressure switch
TC
Boiler thermostat
Tmf 2
stage modulation
nd
thermostat (if present)
TR
Ignition transformer
35
Mains supply
230V-50Hz
TS
Safety thermostat
VP
Main safety valve
VS
2
safety valve
nd
UK

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Em 16/2-l-eEm 26/2-e

Table des Matières