Horizontal Termination - Napoleon Ascent Séries Manuel D'installation

Linéaire. modèles de gaz naturel, modèles de propane. pour usage intérieur seulement
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

3.6

horizontal termination

Simple venting configuration (only one 90° elbow)
For vent configurations requiring more than one 90° elbow, the following formulas apply:
f i r e - p a r t s . c o m
Formula 1: H
< V
T
T
Formula 2: H
+ V
< 40 feet (12.2m)
T
T
Example:
V
= 3 ft (0.9m)
1
V
= 8 ft (2.4m)
2
V
= V
+ V
= 3 ft (0.9m) + 8 ft (2.4m) = 11 ft (3.4m)
T
1
2
H
= 2.5 ft (0.8m)
1
H
= 2 ft (0.6m)
2
H
= H
+ H
= 2.5ft (0.8m) + 2 ft (0.6m) = 4.5 ft (1.4m)
R
1
2
H
= .03 (two 90° elbows - 90°) = .03 (180° - 90°) = 5.4 ft (1.7m)
O
H
= H
+ H
= 4.5 ft (1.4m) + 5.4 ft (1.6m) = 9.9 ft (3m)
T
R
O
H
+ V
= 9.9 ft (3m) + 11 ft (3.4m) = 20.9 ft (6.4m)
T
T
Formula 1: H
< V
T
T
9.9 ft (3m) < 11 ft (3.4m)
Formula 2: H
+ V
< 40 ft (12.2m)
T
T
20.9 ft (6.4m) < 40 ft (12.2m)
Since both formulas are met, this vent configuration is acceptable.
(H
) ≤ (V
)
T
T
See graph to determine the required vertical rise V
40 (12.2)
39 (11.9)
Required vertical
30 (9.1)
rise in feet
(meters) V
T
20 (6.1)
10 (3.1)
0
Horizontal vent run plus offset in feet (meters) H
The shaded area within the lines represents acceptable
venting requirements
the required horizontal run H
2.5
5
7.5
10
12.5
(0.8)
(1.5)
(2.3)
(3.1)
(3.8)
values for H
and V
T
T
90°
V
2
90°
H
90°
V
1
EN
for
T
.
T
15
17.5
20
(4.6)
(5.3)
(6.1)
T
H
2
1
17
W415-1705 / G / 03.21.19