DIRIS A-20
CARACTéRISTIQuES TEChNIQuES
TEChNICAl ChARACTERISTICS
TEChNICAl ChARACTERISTICS - TEChNISChE DATEN -
CARATTERISTIChE TECNIChE - TEChNISChE EIGENSChAPPEN -
CARACTERíSTICAS TéCNICAS - CARACTERíSTICAS TéCNICAS - 技术特性
GB
CASE
Dimensions: 
Connection: 
IP index: 
weight:
DISPLAy
Type : 
MEASUREMENTS
Three-phase (3 or 4 wires), two-phase (2 wire) and single-phase networks
VOLTAGE (TRMS)
Direct measurement:
Update period:
CURRENT (TRMS)
Via CT with: 
minimum measuring current
Input consumption:  
Display: 
permanent overload:  
intermittent overload:  
Update period:
POWER
  T otal:  
Update period:
FREQUENCy
Update period:
AUXILIARy SUPPLy IEC/CE
110 to 400 V AC 50/60 Hz 
120 to 350 V DC  
Consumption: 
42
DIRIS A-20 - Ref.: 535746C
96 x 96 x 60 mm
or 96 x 96 x 80 mm with all optional modules (DIN 43700)
via 2.5 mm
disconnectable terminals
2
(voltage and others) and 6 mm
IP52 (front panel) and IP20 (case)
400 gr.
backlit LCD display
from 110 to 500 v aC (phase/phase)
from 28 to 289 v aC (phase/neutral)
1 second
• Primary:  
up to 9 999 A
• Secondary:  
5 A
5 ma
< 0.6 VA
from 0 to 11 kA (1.1 times the primary value)
6 A
10 In / 1 second
1 second
0 to 11 MW/Mvar/MVA
1 second
from 45,0 to 65,0 Hz
1 second
± 10 %
± 20 %
< 10 VA
 fixed terminals (current)
2