Application conditions
6.2.
Allowable temperatures
Ambient temperature:
max. +55 °C
Heat-radiating energy sources must not additionally heat
the unit.
Permitted medium temperature depending on seal material:
FKM / NBR
0 ... +70 °C
EPDM
-30 ... +70 °C
Permitted medium temperature depending on seal material:
Seal material
FKM / NBR
Diesel and heating oil without addi-
tives, water, compressed air
EPDM
Oil and grease-free liquids and gases,
cold and hot water
Operating duration
Unless otherwise indicated on the rating plate, the solenoid
system is suitable for continuous operation.
Important information for functional reliability during
continuous operation!
If switched on for a long period, it is recommended
to activate the valve 1-2 per day.
12
english
6.4.1.
rating plate
Example:
Orifice
Operating
prinziple
Type
6211EV A 10 EPDM MS
G 1/2 P N 0,5 - 10 bar
230V
00214242
Identification
number
Manufacturer - code
Voltage, frequency, power
consumption
Connection thread, nominal
pressure
14
english
Permitted media
Seal material
Housing material
50-60Hz
4W
W1X LU
Service life
High switching frequency and high pressures reduce the
service life.
6.3.
conformity
CE mark conforms to EMC Directive 2004/108/EEC only if
cables, plugs and sockets connected correctly.
6.4. rating plate description
Rating plate
Fig. 1:
Location of the rating plate
7.
insTallaTiOn
7.1.
safety instructions
Danger!
Risk of injury from high pressure in the equipment!
Before loosening the pipes and valves, turn off the
pressure and vent the pipes.
Risk of injury due to electrical shock!
Before reaching into the device or the equipment,
switch off the power supply and secure to prevent
reactivation!
Observe applicable accident prevention and safety
regulations for electrical equipment!
Warning!
Risk of injury from improper installation!
Installation may be carried out by authorized technici-
ans only and with the appropriate tools!
Risk of injury from unintentional activation of the
system and an uncontrolled restart!
Secure system from unintentional activation.
Following assembly, ensure a controlled restart.