English
Motor cables should have a 360° bond to ensure a low impedance connection, as per the figure below;
Planning Cable Runs
 Use the shortest possible motor cable lengths.
 Use a single length of cable to a star junction point to feed multiple motors.
 Keep electrically noisy and sensitive cables apart. If this is not possible parallel cable runs should be
separated by at least 0.25 meters, for runs longer than 10 meters, separation should be increased
proportionally.
 Sensitive cables should cross noisy cables at 90°.
 Never run sensitive cables close or parallel to the motor, dc link and braking chopper circuit for any
distance.
 Never run supply, dc link or motor cables in the same bundle as the signal/control and feedback cables,
even if they are screened.
Ensure EMC filter input and output cables are separately routed and do not couple across the filter.
Signal
Signal Cable Screen
AC Supply
3
Safety
Earth
Drive Enclosure
2
3
Earth
PE
Motor Cable Screen
2
Typical EMC Connection Diagram