EN
Function
Oil burner pump
SUNTEC
AT2 45
3
6
P
SUNTEC
SUNTEC
SUNTEC
3
2
SUNTEC
1
1
10
www.ecoflamburners.com
SUNTEC
AT3V 45 A
4
7
V
5
1
1
Hoses
2
Filter
3
Oil cock
2
3
8
4
6
V
P
SUNTEC
SUNTEC
3
1
2
1 - INLET
2 - RETURN
3 - BLEED AND PRESSURE GAUGE PORT
4 - VACUUM GAUGE PORT
5 - PRESSURE ADJUSTMENT
6 - TO NOZZLE
7 - PRESSURE ADJUSTMENT
8 - SPECIAL PRESSURE PORT
7
5
The oil burner pump used is a self-priming
gear pump, which must be connected as
two-line pump via a bleed filter. There is an
intake filter and an oil pressure regulator
integrated in the pump. Pressure gauges
for pressure measurements and negative
pressure measurements must be
connected before the equipment is
commissioned.
NB: before starting the burner, check that
the return pipe is open. An eventual
obstraction could damage the pump
sealing device.
AT...: The pump is of the type with two
pressure regimes. During testing it is
calibrated to 10-11 bar low flame and 15-
16 bar high flame.
420010355104