Step
Procedure
1.
Connect the devices and if necessary also the separate supply for the communication
module.
2.
Check the signals at the
communication module ^ 40
3.
Configuration of controllers
connected to the bus
4.
It should now be possible to
communicate with the drive.
5.
Drive-specific settings
6.
Enable controller
7.
Setpoint selection
L
Remarks
-18-
l
At least one of the two status lights (red/greed) at the
device must be on or blinking.
l
The bus LED (green, voltage supply) must be on.
l
The bus LED (yellow, communication LON) indicates
the communication status as described.
Configure the controllers connected to the bus by means
of an appropriate configuration tool
à
e.g. LONMAKERtfor Windows
Use the Service key to sign on the communication
module using the configuratin tool
" LONMakert for Windows® ".
The bus LED (yellow, communication LON) is blinking
when data is exchanged between the 2141
communication module and other devices connected to
the bus.
See the corresponding Operating Instructions
Terminal controller inhibit (CINH) = HIGH
The drive should be running now.
EDKMF2141 DE/EN/FR 2.0
Commissioning
Initial switch-on
®
.
5