Practical Notes

Operation mode
With the potentiometer on the front plate the operartion mode can be
adjustet. The adjustment must be required before energizied. Adjustment
during energization is not allowed.
Only an automatic start at safety function two-hand control (3) is possible.
Start
Fkt. 1
Fkt. 2
1
MANUAL
MANUAL
2
MANUAL
AUTO
3
AUTO
HAND
4
AUTO
AUTO
MANUAL with common
5
button
Fkt. 1:
For manual start S21 must be connected via a pushbutton to ST1. For auto
start S21 has to be linked to ST1
Fkt. 2:
For manual start S41 must be connected via a pushbutton to ST2. For auto
start S41 has to be linked to ST2.
Line fault detection e.g. monitoring of ON-button
If the On-button pressed more than 3 s the adequate output contacts of the
safety function can't be switch. The output contacts can be energized when
the On-button pressed again (0.1 s < t
A line fault is detected if the On-button more than 10 s is actuated. The
output contacts of the adeauate safety function can only be energized with
a reset or re-start with on an off switching of power supply.
Reset and external failures:
The reset input is used to reset external failures (application failures or
removable external failures as e.g. a line fault on reset button). If the reset
signal is connected to the input for more than 3 sec the unit unit makes a
reset. A new reset is only possible when the reset signal had been switched
off temporarily.
If an external failure occurs because both input channels of a safety function
did not switch on or off within the simultanious time, a reset is only possible
if both channels are switched to off state after removing failure cause.
If an external failure occurs in only one safety function, only this function
will be disconnected. The second safety function still continuous to work.
Function setting
The variants with selectable safety functions have 2 potentiometers Fkt.1
and Fkt.2 to select the required function. The following functions are possible:
Fkt. 1 / Fkt. 2
Safety function
1
2
Safety gate
3
Two-hand control
4
Safety mat / Safety edge
5
Exclusive or contacts
6

Operating Potentiometer

7
Safety gate
Poti "t
"
8
Light curtain
Fkt
Poti "t
"
max
Poti "t"
< 3 s).
ON
E-Stop
cross fault detection
E-Stop
without
cross fault detection
Adjustment of delay function
Adjustment of time range
Fine adjustment at time range

Technical Data

Input
Nominal voltage U
:
N
Voltage range:
Nominal consumption:
Short-circuit protection:
Overvoltage protection:
Duty-cycle ON button:
Duty-cycle Reset button:
Safety function
Safety mat / safety edge (4)
max. permitted
safety edge contact resistance: 1000 Ω
switching current at short circuit: Typ. 15 mA at U
Light curtains (8)
control current via S12, S22
e.g. S32, S42:
Min. voltage on terminals
S12, S22 e.g. S32, S42
when relay activated:
Output
Contacts
The NO contacts can be used for safe braking.
Thermal current Strom I
:
th
Safety function
E-Stop (1) (6), Safety gate (2) (7),
Exclusive or contacts (5)
Start up at U
:
N
Release delay at U
and
N
disconnecting the supply:
Release delay at U
and
N
disconnecting S12,S22 or
S32, S42:
Simultaneity demand:
Two-hand control (3)
Start up at U
:
N
Release delay at U
and
N
disconnecting the supply:
Release delay at U
and
N
disconnecting S12,S22 or
S32, S42:
Simultaneity demand:
Safety mat (4)
Start up at U
:
N
Release delay at U
and
N
disconnecting the supply:
Release delay at U
and
N
disconnecting S12,S22 or
S32, S42:
Light curtains (8)
Start up at U
:
N
Release delay at U
and
N
disconnecting the supply:
Release delay at U
and
N
disconnecting S12,S22 or
S32, S42:
Simultaneity demand:
Switching capacity
to AC 15
to DC 13
1. safety function:
2. safety function:
to DC 13
1. safety function:
Electrical life
at 5 A, AC 230 V cos j = 1:
Permissible operating frequency
1. safety function:
2. safety function:
Short circuit strength
max. fuse rating:
Mechanical life:
Semiconductor monitoring output
(not safety):
19
DC 24 V
0.8 ... 1.1 U
N
Typ. 3.2 W
Internal PTC
Internal VDR
0.1 s < t
< 3 s
EIN
> 3 s
N
Typ. 8 mA at U
N
DC 10 V
2 NO contacts per safety function
Max. 8 A
(see quadratic total current limit curve)
< 65 ms
< 40 ms
< 60 ms
< 3 s
< 110 ms
< 40 ms
< 60 ms
< 0.5 s
< 85 ms
< 40 ms
< 60 ms
< 35 ms
< 40 ms
< 25 ms
< 1 s
3 A / AC 230 V
IEC/EN 60947-5-1
2 A / DC 24 V
IEC/EN 60947-5-1
3 A / DC 24 V
IEC/EN 60947-5-1
4 A / DC 24 V at 0.1 Hz
> 1.5 x 10
5
switching cycles
max. 1800 switching cycles / h
max. 360 switching cycles / h
6 A gG /gL
IEC/EN 60947-5-1
10 x 10
switching cycles
6
1 per safety function
max. 50 mA DC 24 V, plus switching
(see quadratic total current limit curve)
UG 6970 / 08.07.19 en / 214A