CHAPTER 3
FAULT /ERROR
Faults
Information
Infos
Info 1
Filter change
Info 2
Frost protection Heat exchanger
Info 3
SD card error
Info 4
Failure of an external module
Error messages
Error 1
Speed error "Supply air" fan (outside air)
Error 2
Speed error "Extract air" fan (outgoing air)
Error 3
-free-
Error 4
SD card error when writing
Error 5
Bus overcurrent
Error 6
-free-
Error 7
BASIS VHZ EH voltage to heat module not available
Error 8
Ext. module (VHZ) mains voltage to KWL-EM unavailable
Error 9
Ext. module (NHZ) mains voltage to KWL-EM unavailable
Error 10
BASIS Int. temp sensor (T1) -outside air- (missing or cable break)
Error 11
BASIS Int. temp sensor (T2) -supply air- (missing or cable break)
Error 12
BASIS Int. temp sensor (T3) -extract air- (missing or cable break)
Error 13
BASIS Int. temp sensor (T4) -outgoing air- (missing or cable break)
Error 14
BASIS Int. temp sensor (T1) -outside air- (short-circuit)
Error 15
BASIS Int. temp sensor (T2) -supply air- (short-circuit)
Error 16
BASIS Int. temp sensor (T3) -extract air- (short-circuit)
Error 17
BASIS Int. temp sensor (T4) -outgoing air- (short-circuit)
Error 18
Ext. module configured as VHZ but not available or malfunction
Error 19
Ext. module configured as NHZ but not available or malfunction
Error 20
Ext. module (VHZ) duct sensor (T5) -outside air- (missing or cable break)
Error 21
Ext. module (NHZ) duct sensor (T6) -supply air- (missing or cable break)
Error 22
Ext. module (VHZ) duct sensor (T7) –return WW register- (missing or cable break) Temp. sens. not sending signal to circ. board Connect temperature sensor correctly
Error 23
Ext. module (VHZ) duct sensor (T5) -outside air- (short circuit)
Error 24
Ext. module (NHZ) duct sensor (T6) -supply air- (short circuit)
Error 25
Ext. module (VHZ) duct sensor (T7) –return WW register- (short circuit)
Error 26
Ext. module (VHZ) safety limiter automatically triggered
Error 27
Ext. module (VHZ) safety limiter manually triggered
Error 28
Ext. module (NHZ) safety limiter automatically triggered
Error 29
Ext. module (NHZ) safety limiter manually triggered
Error 30
Ext. module (NHZ) Frost protection measured by WW return (T7)
(switching threshold adjustable e.g. < 7 °C)
Error 31
Ext. module (NHZ) Frost protection measured by supply air sensor (T6)
(switching threshold adjustable e.g. < 7 °C)
Error 32
Frost protection external WW reg (fixed < 7 °C only PHI) measured either
by (1.) Ext. module (NHZ) supply air duct sensor (T6)
by (2.) BASIS supply air duct sensor (T2)
Comfort controller KWL-BEC

3 .0 KWL-BEC fault overview

Cause
Filter dirty
Cold outside temperature
SD card inserted incorrectly / defective
Cable break,
programmed but unavailable
Target speed is not reached in terms of
ventilation
Software error
Cable break
Motor/impeller defective
Like "Error 1" (see above)
Internal error
Too many subscribers connected to bus
Electronic error
EM module pre-heater with no power
EM module auxiliary heater with no power
Temp. sens. not sending signal to circ. board Connect temperature sensor correctly
Temp. sens. not sending signal to circ. board Connect temperature sensor correctly
Temp. sens. not sending signal to circ. board Connect temperature sensor correctly
Temp. sens. not sending signal to circ. board Connect temperature sensor correctly
Short-circuit in sensor cable
Short-circuit in sensor cable
Short-circuit in sensor cable
Short-circuit in sensor cable
Pre-heater programmed, but corresponding
EM module not connected
Auxiliary heater programmed, but correspon-
ding EM module not connected
Temp. sens. not sending signal to circ. board Connect temperature sensor correctly
Temp. sens. not sending signal to circ. board Connect temperature sensor correctly
Short-circuit in sensor cable
Short-circuit in sensor cable
Short-circuit in sensor cable
Pre-heater coil has overheated!
Bridge not connected or missing
Pre-heater coil has overheated!
Bridge not connected or missing
Auxiliary heater coil has overheated!
Bridge not connected or missing
Auxiliary heater coil has overheated!
Bridge not connected or missing
Return temperature too low
Supply air temperature too low
Supply air temperature too low
27
Solution
Change filter
for info, turns off automatically in war-
mer temperatures
Have SD card tested by specialist
Have programming and connection to
KWL-EM tested by specialist
Check air ducts for obstructions
(dirty grille/filter, incorrectly installed
valves,...)
Reset (electricity off/on)
Connect cable correctly
Replace motor/impeller unit
Like "Error 1" (see above)
Reset (electricity off/on)
Reset (electricity off/on)
Connect/switch on power
Connect/switch on power
Connect temperature sensor correctly
Connect temperature sensor correctly
Connect temperature sensor correctly
Connect temperature sensor correctly
Reprogramme pre-heater or configure
KWL-EM as pre-heater
Reprogramme auxiliary heater or confi-
gure KWL-EM as pre-heater
Connect temperature sensor correctly
Connect temperature sensor correctly
Connect temperature sensor correctly
System automatically resets itself after
cooling
Find cause of overheating
(volume flow too low,..)
Reset (electricity off/on)
Find cause of overheating
(volume flow too low,..)
Auto. system reset after cooling
Find cause of overheating
(volume flow too low,..)
Reset (electricity off/on)
Find cause of overheating
(volume flow too low,..)
Check flow temperature, increase if ne-
cessary, outside temperature too cold
Check flow temperature, increase if ne-
cessary, outside temperature too cold
Check flow temperature, increase if ne-
cessary, outside temperature too cold