3
DMX
According to IEC 60947-3 DMX
Poles number
Rated uninterrupted current (In) [A]
Isolation voltage (Ui) [V]
Rated impulsive voltage (Uimp) [kV]
Service voltage at 50/60Hz (Ue) [V]
Utilization category
Frame
Rated short circuit making capacity (kA)
Rated short-time withstand current Icw (kA) t=1s
Rated short-time withstand current Icw (kA) t=3s
Isolation capability
Endurance (cycles)
Opening time
Closing time
Visualization breakers open/close
Visualization of contacts position
Visualization of charged/discharged springs
Signalling contacts
Shunt trip
Closing coil
Undervoltage release
Undervoltage release with time delay
Motor operator
Mechanical interlock
* Standard version with n° 4 NO/NC (max n° 6 optional contacts 288 15).
S=Standard
O=Optional
SWITCH DISCONNECTORS
3
category
230V ÷ 500Va.c.
600Va.c.
690Va.c.
230V ÷ 500Va.c.
600Va.c.
690Va.c.
230V ÷ 500Va.c.
600Va.c.
690Va.c
without maintenance
mechanical
with maintenance
electrical
without maintenance
DMX
3
-I 2500 DMX
3
-I 4000 DMX
3P-4P
3P-4P
1250÷2500 3200-4000
1000
1000
12
12
690
690
AC23-DC23 AC23-DC23 AC23-DC23
1
2
143
220
132
165
121
143
65
85
60
75
55
65
45
65
45
65
45
65
yes
yes
10000
10000
20000
20000
10000
10000
15 ms
15 ms
30 ms
30 ms
S
S
S
S
S
S
S *
S *
O
O
O
O
O
O
O
O
O
O
O
O
3
-I 6300
3P-4P
6300
1000
12
690
3
220
165
143
100
75
65
85
75
65
yes
5000
10000
5000
15 ms
30 ms
S
S
S
S *
O
O
O
O
O
O
85