18. New cabling system

New automatic "Cage Clamps".
Constant press on cable guarantee maximum contact
during time.
This is the solution to the problem of screw with 1/2 turn.
Shape form of spring avoid the problem of incision of
insulation.
To have a major order and safety when cabling
operations are done, the draw-out version of the DMX
120
3
SUGGESTED CABLE DIMENSIONS
LENGTH
A: <8mm - length not sufficient
B: ≥8mm and ≤10mm - optimal length
C: >10mm and ≤12mm - acceptable length
D: >12mm and ≤14mm - length possible but not
safe for insulation reason
E: >14mm - length not safe for insulation reason
1. Put the screw: the clamp open.
2. Put the cable.
3. Extract the screw: clamp automatically lock the cable.
Detail: Electrical contact is guaranteed with max
flexible cable diameter up to 2,5 mm
cable of different sections.
SECTION
–Rigid 1mm²
–Rigid 1,5mm²
–Rigid 2,5mm²
–Flexible 1mm² *
–Flexible 1,5mm² *
–Flexible 2,5mm² *
–Flexible 1mm² with ferrules
–Flexible 1,5mm² with ferrules
–Flexible 2,5mm² with ferrules**
has several buttonholes usefull to collect all the cables
3
with cable ties as shown.
2
, also with two
Detail
A
B
C
D
E
*
with a screwdriver
** without insulating flange