Important Installation Requirements
Failure to comply with these requirements will result in voided warranty, improper installation, and
service callbacks.
Personal Safety
•
Wear safety glasses while installing TrueSTEAM.
•
Do not cut into any air conditioning or electrical line.
•
Follow professional safety standards and all local regulations.
Mounting Location
•
Mount TrueSTEAM in a level position to avoid water damage or heating element failure.
•
Install TrueSTEAM on the supply duct. Use the Remote Mounting Kit if duct mounting is not possible.
•
Do not install TrueSTEAM where the ambient temperature is lower than 34°F (1.1°C) or higher
than 104°F (40°C).
•
Mounting area must be strong enough to support TrueSTEAM's weight when full of water (up to 15 lbs.).
•
Choose a location that is well ventilated. Do not install TrueSTEAM in completely enclosed spaces, such as a
cabinet or unventilated closet.
•
Allow at least 1 foot clearance to ventilation holes in the TrueSTEAM cover. Do not cover the holes. Covering
them can increase the temperature inside TrueSTEAM and shorten its life.
•
Do not mount directly to duct board. The remote mount nozzle attachment is allowed only with a Honeywell
duct board adapter kit. See "Appendix B: Parts List" on page 35.
•
If used near a pool or spa, make sure TrueSTEAM can not fall into the water or be splashed. Also, ensure
TrueSTEAM is plugged into a ground fault interrupted (GFI) outlet.
Duct Nozzle
•
Do not install the duct nozzle into a supply duct with static pressure exceeding 0.5 in. w.c.
•
Do not install the duct nozzle through wooden sidewalls (e.g., floor joist).
•
If the duct has exposed insulation on the interior, be sure the nozzle extends beyond the insulation. Clear
away excess insulation at the insertion point, or replace a section of insulated duct (approximately 6 in. x
6 in.) with rigid, non-insulated sheet metal.
•
Allow at least 4 in. clearance between nozzle outlet and any interior duct to avoid water condensation.
•
Mount TrueSTEAM where the nozzle outlet has a minimum 24 in. of downstream open air space.
Water Drainage
•
Consult local plumbing codes for drain size, material, and maximum temperature allowed.
4
TrueSTEAM Humidification System 69-2285EF—01