2
2.2
[Fig. 2.2.1]
A Inspection hole
B Side of outdoor unit piping
C Control box
D Side of indoor unit piping
E Water inlet
F Service space
G Indoor unit side
*1 Dimensions with which pipe connection can be handled at site
[Fig. 2.4.1]
CMB-WP108V-GA1 + CMB-WP108V-GB1
(CMB-WP1016V-GA1) (CMB-WP1016V-GB1)
A
A
H
a
D
b
A Outdoor unit
C Sub-HBC controller
E Less than H=50 m (when the outdoor unit is higher than HBC)
F Less than H1=40 m (when the outdoor unit is lower than HBC)
G Twinning pipe (field supply)
H Less than 110 m
J Up to three units for 1 branch port
Total capacity: less than 80 (but in same mode, cooling/heating)
K Less than 15 m
[Fig. 2.4.2]
CMB-WP108V-GA1 + CMB-WP108V-GB1
(CMB-WP1016V-GA1) (CMB-WP1016V-GB1)
A
H
A
B
G
a
D
b
A Outdoor unit
C Sub-HBC controller
E Less than H=50 m (when the outdoor unit is higher than the indoor unit)
F Less than H1=40 m (when the outdoor unit is lower than the indoor unit)
G Twinning pipe (field supply)
H Less than 110 m
J Up to three units for 1 branch port
Total capacity: less than 80 (but in same mode, cooling/heating)
K Less than 15 m
M Less than 15 m
2
[Fig. 2.3.1]
<A>
<B>
I
B
C
f
G
c
g
d
e
D
D
D
J
D
B Main-HBC controller
D Indoor unit
I Less than 60 m
L Less than 15 m
B
D
I
B
C
f
G
c
g
d
e
D
D
D
J
D
B Main-HBC controller
D Indoor unit
I Less than 60 m
L Less than 15 m
B
300
B
A
A
450□
450□
C
F
Service space
D
G
Indoor unit side
F
Service space
A
F
Service space
B
F
Service space
2.4
Notes:
*1 Indoor units that are connected to the same branch joint cannot be si-
multaneously operated in different operation modes.
Between outdoor unit and
HBC controller (refrigerant pipework)
Water pipework between indoor units
and HBC controller
Between
indoor and
outdoor units
Between indoor units and HBC controller
Between indoor units
Between outdoor unit and
HBC controller (refrigerant pipework)
Water pipework between indoor units
and HBC controller
Between HBC controllers
Between
indoor and
outdoor units
Between indoor units and HBC controller
Between indoor units
Between HBC controllers
2.3
Model name
CMB-WP108V-GA1
CMB-WP1016V-GA1
CMB-WP108V-GB1
CMB-WP1016V-GB1
E
Item
Piping portion
A
f + g
Above outdoor unit
H
Below outdoor unit
H1
h1
h2
Item
Piping portion
A
f + g
B
Above outdoor unit
H
Below outdoor unit
H1
h1
h2
h3
<A> Top view
<B> Front view
A
B
1520
160
1800
300
1520
160
1520
160
(Unit: m)
Allowable value
110 or less
60 or less
50 or less
40 or less
15 or less
15 or less
(Unit: m)
Allowable value
110 or less
60 or less
40 or less
50 or less
40 or less
15 or less
15 or less
15 or less