3.3.3. Suitable for heavy load traffic (SLW40, cover D400)
A load distribution plate ④ (property class
C40/50)
must
telescope for installations in areas with heavy
load traffic. A respective form- work and
reinforcement plan is available from the
manufacturer. An adequately compacted,
anti-capillary and draining base course must
be installed underneath the load distribution
plate. A geotextile must be laid horizontally at
the level of the tank opening. Afterwards, a
tubular seal ② is inserted into the groove of
the telescopic dome shaft for trucks ③. At
last, the concrete cover ① is placed onto the
telescopic dome shaft.
3.4.
Commissioning
If there is not already one in place, the nameplate delivered with every separator must be
attached via a chain to the under- side of the telescopic dome shaft cover. To
commission the separator, fill it with grease-free and oil-free water until the water begins
to flow out of the discharge pipe.