Remote Maintenance Bypass - ALLTRONIC SEMIS T33 Manuel D'installation

Masquer les pouces Voir aussi pour SEMIS T33:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

R
EMOTE MAINTENANCE BYPASS
Attention
The "SERVICE BYPASS" (see "UPS connections view") terminal absolutely must be connected to the
auxiliary contact of the REMOTE MAINTENANCE BYPASS SWITCH (3). When this switch closes, an auxiliary
contact signalling insertion of the remote bypass to the UPS must open. Failure to perform this connection
can cause power cut-off to the load and UPS damage.
REMOTE MAINTENANCE BYPASS INSTALLATION DIAGRAM
- 84 -