EMOTE MAINTENANCE BYPASS
Caution
The "SERVICE BYPASS" terminal (see "Auxiliary contacts section") must be connected to the auxiliary
contact of the REMOTE MAINTENANCE BYPASS SWITCH (3). When this switch closes, an auxiliary contact
signalling insertion of the remote bypass to the UPS must open. Failure to perform this connection can
cause power cut-off to the load and UPS damage.
REMOTE MAINTENANCE BYPASS INSTALLATION DIAGRAM
"Installation Instructions"
"Installation Instructions",
- 80 -