UPS Models
INPUT STAGE
Nominal Voltage
Nominal Frequency
Maximum input current
(1)
Maximum battery current
Input voltage tolerance accepted for
no battery intervention (referred to
400V AC)
Input frequency tolerance accepted
for no battery intervention (referred
to 50/60Hz)
Input current Harmonic Distortion
Input power factor
Power Walk In mode
OUTPUT STAGE
Nominal Voltage
(3)
Nominal Frequency
(4)
Output nominal current
Nominal apparent power in output
Nominal active power in output
Output power factor
Short-circuit current
Output voltage precision (referred to
output voltage 400V AC)
(5)
Static stability
Dynamic stability
Output voltage harmonic distortion
with linear load and normalized
distortion
Crest factor accepted at nominal
load
Frequency accuracy in free running
mode
Inverter overload (Vin>345V AC )
Bypass Overload
BATTERY CHARGE STAGE
Nominal voltage
Maximum recharging current
TECHNICAL DATA
SEMIS 60 NP
96A
150A
87A
60kVA
54kW
≤ 1% with linear load
≤ 3% with distorted
load
(7)
SEMIS 80 NP
380-400-415 V AC Three-phase with neutral (4 wire)
50-60Hz
125A
200A
± 20% @ 100% load
-40% +20% @50% load
± 20%
40-72Hz
THDi = 2.5%
(2)
≥ 0.99
Programmable from 1 to 125 sec. at steps of 1 sec
380/400/415 V AC three-phase with neutral (4 wire)
50/60Hz
116A
80kVA
72kW
0.9
1.5 x In for t > 500ms
± 1%
± 0.5%
± 3% resistive load
≤ 1% with linear load
≤ 3% with distorted
≤ 3,5% with distorted
load
3:1
0.01%
103% Infinite, 110% 10 min, 125% 1 min
110% Infinite,125% 60 minutes, 150% 10 minutes
±240Vdc
10A (20A optional)
- 108 -
SEMIS 100 NP
SEMIS 125 NP
155A
250A
THDi ≤ 2,5%
145A
100kVA
90kW
(6)
≤ 1% with linear load
≤ 1% with linear load
≤ 3% with distorted
load
211A
300A
(2)
181A
125kVA
112.5kW
up to a 2,7 x In
load
25A