PROBLEM
THE DISPLAY SHOWS
C01
THE DISPLAY SHOWS
C05
THE DISPLAY SHOWS
ONE OR MORE OF THE
FOLLOWING CODES:
A30, A32, A33, A34
THE UPS WILL NOT
START UP
THE DISPLAY SHOWS
ONE OR MORE OF THE
FOLLOWING CODES:
F09, F10
THE DISPLAY SHOWS
ONE OR MORE OF THE
FOLLOWING CODES:
F11, F14, F15, F16, F17,
L06, L07, L08, L09, L14,
L15, L16, L17, L18, L19,
L20, L21, L22
THE DISPLAY SHOWS
ONE OR MORE OF THE
FOLLOWING CODES:
F03, F04, F05, A08, A09,
A10
THE DISPLAY SHOWS
ONE OR MORE OF THE
FOLLOWING CODES:
F42, F43, F44, L42, L43,
L44
POSSIBLE CAUSE
NO JUMPER ON R.E.P.O.
CONNECTOR (SEE
"COMMUNICATIONS AREA
VIEW") OR JUMPER NOT
INSERTED PROPERLY
MANUAL BYPASS SWITCH
(SWMB) CLOSED
NO JUMPER ON TERMINALS
FOR REMOTE MAINTENANCE
BYPASS (A3-A4, "UPS
CONNECTIONS VIEW")
AMBIENT
TEMPERATURE < 0°C
TEMPERATURE SENSOR
MALFUNCTION ON
DISSIPATOR
UPS INPUT STAGE
MALFUNCTION
PHASE 1 PRESENTS
VOLTAGE MUCH LOWER
THAN THE OTHER TWO
PHASES.
INSERTION OF ABNORMAL
LOADS
UPS INPUT OR OUTPUT
STAGE MALFUNCTION
NO CONNECTION ON ONE OR
MORE PHASES
FUSES BROKEN INSIDE
PROTECTIONS ON PHASES
OR INPUT CONTACTOR
FUSES BROKEN INSIDE
PROTECTIONS ON
BATTERIES
- 101 -
SOLUTION