PROBLEMA
IL DISPLAY INDICA C01
IL DISPLAY INDICA C05
IL DISPLAY VISUALIZZA
UNO O PIÙ DEI
SEGUENTI CODICI:
A30, A32, A33, A34
E L'UPS NON PARTE
IL DISPLAY VISUALIZZA
UNO O PIÙ DEI
SEGUENTI CODICI:
F09, F10
IL DISPLAY VISUALIZZA
UNO O PIÙ DEI
SEGUENTI CODICI:
F11, F14, F15, F16, F17,
L06, L07, L08, L09, L14,
L15, L16, L17, L18, L19,
L20, L21, L22
IL DISPLAY VISUALIZZA
UNO O PIÙ DEI
SEGUENTI CODICI:
F03, F04, F05, A08, A09,
A10
IL DISPLAY VISUALIZZA
UNO O PIÙ DEI
SEGUENTI CODICI:
F42, F43, F44, L42, L43,
L44
POSSIBILE CAUSA
MANCA IL PONTICELLO SUL
CONNETTORE R.E.P.O. (VEDI
"VISTA ZONA
COMUNICAZIONI") OPPURE
NON È INSERITO
CORRETTAMENTE
SEZIONATORE BYPASS
MANUALE (SWMB) CHIUSO
MANCA IL PONTICELLO SUI
MORSETTI PER BYPASS
MANUTENZIONE REMOTO
(A3-A4, "VISTA CONNESSIONI
UPS")
TEMPERATURA
AMBIENTE < 0°C
MALFUNZIONAMENTO DEL
SENSORE DI TEMPERATURA
SUL DISSIPATORE
MALFUNZIONAMENTO NELLO
STADIO DI INGRESSO
DELL'UPS
LA FASE 1 PRESENTA UNA
TENSIONE MOLTO MINORE
DELLE ALTRE DUE FASI.
INSERIMENTO DI CARICHI
ANOMALI
MALFUNZIONAMENTO DELLO
STADIO DI INGRESSO O DI
USCITA DELL'UPS
MANCANZA DEL
COLLEGAMENTO SU UNA O
PIÙ FASI
ROTTURA DEI FUSIBILI
INTERNI DI PROTEZIONE
SULLE FASI O DEL
TELERUTTORE DI INGRESSO
ROTTURA DEI FUSIBILI
INTERNI DI PROTEZIONE
SULLE BATTERIE
- 47 -
SOLUZIONE