Advanced settings
Parameter
Name
Vmin boost
Imax in motor mode
2
Motor overload setting (I
xt)
Starting value for motor
2
overload (I
xt)
Motor brake switching
threshold
Brake resistor R
Rated power of brake resistor
Thermal capacity of brake
resistor
Reduction of brake chopper
threshold
Impact of oscillation damping
Oscillation damping filter time 50 ms
Logbook
Parameter
Name
Error message 1 (last)
Error message 2
Error message 3
Error message 4 (earliest)
Meters
Parameter
Name
Elapsed−hour meter
Operating−hour meter
Lenze ¯ MDKSEMA ¯ 5.0
Value
Delivery
Setting range
0.0 %
[0.0 ... 100.0] %
Device−depende
[0.00 ... Imax] A
nt
100.00 %
[0.00 ... 250.00] %
50.00 %
[0.00 ... 100.00] %
100 rpm
[0 ... 499.9/i] rpm
− ohms
[150.0 ... 500.0] ohms
− W
[10 ... 65535] W
− kWs
[0 ... 6553.5] kWs
0 V
[0 ... 150] V
5.00 %
[0.00 ... 250.00] %
[2 ... 250] ms
Value
Delivery
Setting range
[text]
[text]
[text]
[text]
Value
Delivery
Setting range
[0 ... 596523] h
[0 ... 596523] h
Commissioning
Parameter list
Comment
Effective only if Energy saving function = On:
¯ Boost of the motor voltage in the range of
low speeds.
¯ In the case of conveyor applications with
an inclined proportion, a turn−back during
start−up can be prevented.
¯ Typical values approx. < 5%.
Maximum motor current
MSEMAxx063−42: 5.6 A
MSEMAxx080−32: 13.2 A
With a gearbox, the setting range can be
smaller.
Reduction of I
limits the load−dependent
max
starting torque.
Setting for operation at an ambient
temperature of up to + 40 °C optimised.
Recommended setting for operation
according to UL: 50.00 %
Motor brake is switched if the value is
exceeded or is too low.
Higher value:
In the case of conveyor applications with an
inclined proportion, a turn−back during
start−up can be prevented.
Enter data of a connected brake resistor
correctly.
If fitted in the factory:
¯ In case of internal brake resistors, the
values of the brake resistor are preset.
From FW 02.02.00.00, the retrofitting and
adaptation of the parameters to an
external brake resistor are possible.
¯ If an external brake resistor is used, the
values of the brake resistor are preset.
Only the rated power can be increased
from 20 W to a maximum of 40 W if the
mean speed is > 1000 r/min
(mathematical mean of the process speeds
in relation to the motor speed, without
standstill).
The threshold is reduced by the voltage value
set here.
The switching threshold is adapted to the
different mains voltage ranges.
Reduction by 20 ... 30 V can prevent
overvoltage for operation in generator mode.
To suppress idle oscillations. Typically, the
impact has to be increased for this purpose.
Comment
Meaning: see fault message table
Comment
Total time of "Motor rotating"
Total time of "mains ON"
5
EN
43