For installations in areas subject to explosion hazards, special
regulations apply!
APPLICATION
If the pump is sluggish, fill the pump with water and start the
pump several times, if necessary.
Breeze pressure pipe and pump sump aeration systems are
used in pressure drainage systems and wastewater pipelines.
These systems convey oxygen into the wastewater and in this
way reduce corrosion of the concrete and help prevent the for-
mation of hydrogen sulphide. The pressure pipe must be laid
with a positive gradient throughout its length.
The control unit cannot withstand submersion, but is splash-
proof in accordance with IP 44.
If installed in compliance with the regulations and used prop-
erly, then this control unit meets the protective requirements
of the EMC Directive 2014/30/EU and is suitable for domestic
use and connection to a power supply from the grid. When
connected to an industrial mains within an industrial operation
with power supply provided by a company-own high-voltage
transformer, insufficient immunity to interference has to be
expected.
When using the pumps, the relevant national laws, regulations
and stipulations must be adhered to, for example:
• Installation of low voltage systems (e.g. VDE 0100 in Ger-
many)
• Safety and working materials (e.g., BetrSichV and BGR 500
in Germany)
• Safety in wastewater systems (e.g., GUV-V C5, GUV-R 104 and
GUV-R 126 in Germany)
• Electrical systems and operating resources (e.g., GUV-V A3
in Germany)
• Explosion protection EN 60079-0: 2012, EN 60079-1:2007,
EN 60079-14:2007, EN 60079-17:2007 and EN 1127-1:2011

Scope of supply

• Plastic box with separate plinth
• Compressor(s)
• Flushing device
• 5 m pressure hose
• Control
• only for pump sump ventilation (PSV): Aeration hose with fix-
ing materials
10
INSTALLATION
NOTICE! The connection to the wastewater pressure pipe
must be accommodated in the pump chamber, the connection
chamber or in a building provided by the customer at a frost
free depth.
NOTICE! It is not permissible to pull the pressure pipe upwards
into the box and connect it to the Breeze SH there.
If the box is moved, the bottom of the base must be filled with
approx. 5 cm of dry white sand above the ground level to avoid
condensation from developing.
The empty conduit for the pressure hose and the mains con-
nection must be closed off with a sealing plug to prevent mois-
ture from penetrating, for example, from the pump chamber.
NOTICE! Moisture in the control can result in functional faults
or even breakdown. The normal ventilation of the box is unable
to dry out the control.
The ventilation openings in the box must remain free and must
not be covered by plants or structures.
Connecting to the wastewater pipe
The compressed air hose is routed through an empty conduit
to the connection socket for the wastewater pipe.
NOTICE! Do not bend the hose, and lay the hose with a gradient
into a frost free depth.
The compressed air must be dispensed after the non-return
valve in the wastewater pipe, as air must not be allowed to en-
ter the sewage pump.