great that the contents of the pressure pipe are renewed in the
exchange time (generally 2 hours), it is not necessary to flush
out the pipes. Otherwise, flushing is necessary. If at the same
time fixed flushing times are set, it is possible to determine
that the unit should start up only if a minimum interval to the
next fixed flushing time is adhered to.
△▽ Volume PPL -OK-
Calculate NO (direct entry) / YES
△▽ Sections per pipe x (1-5) -OK-
Number can be determined.
△▽ Section 1 data -OK
Calculate NO (direct entry) / YES
△▽ Section length 1 -OK-
△▽ Section dia. 1 -OK-
△▽ Section 2 data -OK
Calculate NO (direct entry) / YES
△▽ Section length 1 -OK-
△▽ Section dia. 1 -OK-
△▽ Section ...
△▽ Vol. per pumping proc -OK-
Calculate NO (direct entry) / YES
Height difference -OK-
Pump sump dia. -OK-
△▽ Exchange time -OK-
△▽ Minimum interval -OK-
▲ ▼ PPCS after run -OK-
In this case, the unit runs after the sewage pump. Each flas-
hing digit must be selected with the arrow button and confir-
med with -OK-.
After run in seconds (0-999)
▲ ▼ PSV -OK-
To extend the anaerobic state of the wastewater, a pump sump
aeration unit can be installed. The duty cycle and pause time
are then defined in this menu. Each flashing digit must be se-
lected with the arrow button and confirmed with -OK-.
△▽ Duty cycle -OK-
△▽ Pause time -OK-
▲ ▼ PPV -OK-
The aeration time and the number of cycles can be set for
these components. Please refer to the tables in the appendix
for the values which are specified depending upon the pres-
sure pipe, pressure pipe length and the system pressure.
▲ ▼ Lock out periods -OK-
Times can be set here during which the unit
must not operate under any circumstances.
△▽ WO1, WO2, WO3, WO4, WO5 (Mon-Fri)
WE1, WE2, WE3, WE4, WE5 (Sat-Sun) -OK-
△▽ Active -OK-
△▽ Start -OK-
△▽ End -OK-
MANUAL MODE -OK-
▲ ▼ Manual flushing -OK-
Pipes 1 - 4
-OK-
Enter running time in secs 0000
Each flashing digit must be selected with the arrow button and
confirmed with -OK-. If the time has been fully set, confirm this
with -OK- or return with -ESC-.
If you do not wish to enter any further pipes, press -ESC- again
and you are now back in the "Handmodus" menu.
▲ ▼ Manual units -OK-
PPCS - pressure pipe cleaning system
PSV - pump sump ventilation
PPV - pressure pipe ventilation
Heat - heating
Vent - ventilation fan
By pressing ▲ ▼ the selected unit can be switched on and off.
This is confirmed in the usual way with -OK-. Press -ESC- to
exit the menu without carrying out any change.
System settings -OK-
You can now select various sub-menus with ▲ ▼ . Once you
press -OK-, you will be asked to enter a password.
The factory default setting is "0000". Each of the four digits
must be confirmed with -OK-. This means that in the case of
the factory default setting, for example, you will have to press
-OK- four times. You are now in the relevant sub-menu.
▲ ▼ Set date -OK-
Each flashing digit must be selected with the arrow button and
confirmed with -OK-. The day of the week is set automatically.
Once the full date has been set, a "Datum ok?" query follows.
Confirm with -OK- or return with -ESC-.
▲ ▼ Set clock -OK-
Each flashing digit must be selected with the arrow button and
confirmed with -OK-. Once the full time has been set, a "Uhrzeit
OK?" query follows. Confirm with -OK- or return with -ESC-.
▲ ▼ Sommer/Wintertime -OK-
The automatic changeover from summer to winter time is
switched on and off here.
▲ ▼ Change password -OK-
All four digits must be confirmed with -OK-. This is followed up
with a final prompt for confirmation. The new password can be
noted in this instruction manual.
_ _ _ _ • _ _ _ _ • _ _ _ _ • _ _ _ _ • _ _ _ _ •
▲ ▼ Service menu -OK-
For the manufacturer only
▲ ▼ Service interval -OK-
The service interval counter can be reset here.
▲ ▼ Reset to default settings -OK-
You can carry out a reset here. The unit will be reset to the fac-
tory default settings and a restart will be carried out.
ENGLISH
-OK-
13