The duration of the action is dictated by system characteristics. Legionella bacteria react differently depending on the maximum
temperature reached in the circuit. The higher the temperature, the shorter the duration.
The control signals the anti-legionella function is running by displaying LEG and exits the function after a maximum of 5 hours,
if for some reason the temperature is not reached inside the tank.
In the event excessive DHW is tapped off during the anti-legionella cycle and the temperature is not maintained, after two
attempts the control exits the function. When the anti-legionella cycle is not completed two consecutive times, alarm A8 is
displayed.
While the anti-legionella function is running, the system's cooling or heating functions are interrupted when the disinfection
cycle is carried out by the heat pump and the electrical heater elements (parameter LdA 0). On the other hand, the heating
or cooling function is not interrupted if the anti-legionella cycle is carried out by an electrical heater element in the domestic
water tank (parameter LdA 1).
To prevent scalding if tapping off hot water during the disinfection cycle, it is advisable to install anti-scalding safety devices
on each utility and at the domestic water tank outlet.
•
FROST-PROTECTION
The internal unit's brazed plates exchanger is protected against freezing by a ow switch, which stops the system when the
water ow is insuf cient, and by two temperature sensors on the plate exchanger, which stop the system when the water
temperatures are too low
•
CLIMATE CURVES ( g. 29)
To optimise energy saving, two climate curves are available: one for heating and one for cooling. This function enables the
water temperature to be adjusted to the outside air temperature and therefore to the heating load, optimising system energy
saving.
The curve is enabled in heating by setting parameter Hcc 1,
The climate curve is set using four parameters:
The climate curve is set using four parameters:
Hc1 outside air temperature to have maximum water temperature
Hc2 maximum water temperature
Hc3 outside air temperature to have minimum water temperature
Hc4 minimum water temperature
The curve is enabled in cooling by setting parameter Ccc 1,
The climate curve is set using four parameters:
Cc1 outside air temperature to have maximum water temperature
Cc2 maximum water temperature
Cc3 outside air temperature to have minimum water temperature
Cc4 minimum water temperature
See g. 29 CLIMATE CURVE HEATING Hcc and COOLING Ccc.
Do not modify parameters CHS, rtF, Adr and FPt; t ey are factory set parameters.
3.5
SETTING THE SERVICE MENU PARAMETERS
Use button E 4
Once the service menu is selected, press E 6
press info/set again for three seconds and 00 ashes, then enter the PAS and press info/set to con rm. Press Menu to display
PAS and use the up and down arrows to view all parameters in the user menu. Press the info/set button again to view the value
of the parameter; on pressing info/set again for three seconds the value on the display ashes and can be modi ed using the
arrows ey1
and ey2
Press menu to exit and the arrows to select another parameter.
Proceed in the same way for the other parameters.
Quit the menu automatically by not pressing any buttons for 60 seconds or by pressing both arrows ey1
simultaneously.
Example:
1.
Press ey4
2.
Press ey6
3.
Press ey6
4.
Press ey6
5.
Press ey1
6.
Press ey6
7.
Press ey4
8.
Press ey1
the display. Stop at the parameter to be modi ed
9.
Press ey6
10.
Press ey1
11.
Press ey6
12.
Press ey4
modify another parameter.
Press ey1
to access the Service menu, pressing it twice displays SEr for Service
, press info/set again to con rm.
twice to view SER on the display
, to view PAS on the display
, to view 00 on the display
, for three seconds, the value 00 ashes on the display
or ey2
, to increase or reduce the value displayed
, to con rm the set value, the display stops ashing
, to exit, PAS is displayed
or ey2
, to view a parameter. The mnemonic symbols of the parameters appear in sequence on
, for three seconds, the parameter value ashes on the display
or ey2
, to change the parameter
, to con rm the set value, the display stops ashing
, to exit, the mnemonic symbol of the last parameter on the display appears; restart from point 8 to
and ey2
simultaneously to quit the user menu.
, to display the password request (PAS); press info/set and 00 displays,
3
and ey2
53