T e minimum nominal diameter of t e ydraulic connecting pipes must be 1".
To allo t e maintenance and repair operations it is indispensable t at eac
tive manual closing valves.
The table below shows the characteristics the hydraulic system must have.
Nominal water
ow*
System water
content
Operating
pressure
System height
difference
*
for systems at ground level
**
with maximum system water temperature 35°C
The graphs in g. 19 show the head, for each hydraulic circulator speed, available to the hydraulic connections of the internal unit.
Check that the system's pressure losses guarantee the required water ow (see sect. 2.10.2).
If greater heads are required due to high pressure losses in the system, an inertial vessel or a hydraulic separator and an external
idle pump must be added.
Check if the system has the minimum water content required to ensure good system operation. If it is insuf cient, add a storage
vessel in order to reach the required content.
The water distribution pipes must be suitably insulated with expanded polyethylene or similar materials. The on/off valves, bends
and unions must also be suitably insulated.
To prevent air locks inside the circuit, insert automatic or manual breather devices at all the points (high pipes, traps etc.) where
air may accumulate.
Once t e ydraulic circuit is complete and t e absence of lea s as been ascertained, remove t e circulation pump
brac et ( g. 20 ref. A) by removing t e fastening nut ( g. 20 ref. B); re t t e nut.
2.5.1
Hydraulic circuit ( g. 21)
The hydraulic diagram in g. 21 shows the main parts of the internal unit and a typical hydraulic circuit.
1
Water inlet
2
Safety valve (3 bar)
3
Pressure gauge
4
System water return temperature probe T1
5
Plate heat exchanger
6
System water ow temperature probe T2
7
Flow switch
8
Expansion vessel
9
Electrical heater elements collector
10 Automatic air breather
11 Circulation pump
12 3-way diverter valve (integrated on board the machine in version 3W)
13 System water outlet
14 Water outlet for domestic water storage
15 Mesh water lter
16 Refrigerant pipe connections
17 Domestic heater temperature probe T3
A
Internal unit
B
External unit
C
System (fan coils, radiators or radiant panels/ oors)
D
Domestic water storage
E
Additional heat source (e.g. gas boiler)
Install a sieve lter with 0.4 mm mesh on the appliance's water inlet pipe (return from system).
44
OS-CEBSH24EI
OS-CEBCH36EI
Unit
I.U. SHERPA SMALL
l/s
0,31
Min
l
23
Max**
l
400
Max
kPa
300
Max
m
20
ydraulic connection is tted it respec-
OS-CEBCH48EI
OS-CEBTH48EI
0,52
0,62
0,62
38
45
400
400
300
300
20
20
OS-CEBCH60EI
OS-CEBTH60EI
I.U. SHERPA BIG
0,69
0,79
45
51
400
400
400
300
300
300
20
20
58
20