10.4 Bohrflächen
Table 10.4.1
Enclosure Face
Top & Bottom
Face A & B
Sides (Left & Right)
Face C & D
Back
Face E
Lid
Face F
Table 10.4.2
Area required per piece
The maximum enclosure entry areas and entry quantities can be calculated from the overall dimensions of the enclosure.
The usable entry area an maximum quantity of entries is calculated using table 10.4.1 and table 10.4.2.
The table 10.4.1 and table 10.4.2. are used to calculate the maximum number of entries allowed on each enclosure face.
For an enclosure side face the sizes are height and depth -25.4 (remove the depth of the lid.).
Subtract the face of edge clearance from each size and multiply by each other.
Finally multiply by the face area factor to give the total usable.
Available glanding area =(Height - 2 * clearance) * (depth - lid depth - 2 * clearance) * Area Factor
For example:
Based on an M20 entry using a surface area of 844 mm², the maximum quantity of
M20 Entries is
This calculation should always be rounded down to the nearest whole number and additional restrictions below should
also be considered.
In addition to the above the following must also be taken into account.
No entry is permitted within 40 mm of an earth stud, a mounting foot or an internal mounting lug.
The calculation takes into account the unusable area with round entries (based on minimum centres, 75% is maximum
area that can be utilised) and practical reductions to maintain functional performance requirements.
10.4 Drilling areas
Percentage of Entry that can be populated & Edge clearance
Smallest up to size 1000x800x400
Face Area Factor
0.70
0.70
0.25
0.30
Standard cable entry area required - Based on Capri ADE 1F
M12
M16
M20
315 mm²
496 mm²
844 mm²
Enclosure 800 mm by 600 mm by 250 mm
Usable right side area:
800 - (2 * 20) * 250 - 25.4 - (2 * 12.5) * 0.70 = 106,187 mm²
106,187 mm² / 844 mm² = 125 pcs
Face Edge Clearance
12.5 mm
/ 20 mm
12.5 mm
/ 20 mm
50 mm
/ 50 mm
50 mm
/ 50 mm
M25
M32
1248 mm²
2548 mm²
10.4 Zones de forage
Size 1001x801x400 up to largest size
Face Area Factor
Face Edge Clearance
0.45
20 mm
0.45
20 mm
0.10
100 mm
0.15
50 mm
M40
M50
4076 mm²
7472 mm²
/ 20 mm
/ 20 mm
/ 100 mm
/ 50 mm
M63
11692 mm²
25