7.11.
Setting the air purging function (Air removal)
After accessing the "Air removal" function, you can
activate water circulation (in the selected circuit) to
eliminate any air from the circuit. Select the required
logic, then press "OK" to confirm.
NOTES:
1.
This function can only be activated if the unit is switched Off. In addition, this function must be disa-
bled before the unit can be switched On.
2.
If the relative function is activated (paragraph 8.3), the value of these parameters will be stored in the
memory and automatically reset after any possible voltage failure.
7.12.
Setting the pre-heating procedure for radiant panels (Floor debug)
After accessing the "Floor debug" function, you can
activate or deactivate any possible procedure for
pre-heating the radiant panels. This procedure creates
a heating cycle during which the temperature is kept
stable for a certain time (period), then increased by a
value equal to ΔT indicated, and kept there for the next
period. This temperature increase and hold procedure
will be repeated for the number of periods specified.
At the end, press the button at the top right to start (or
interrupt) the pre-heating cycle.
NOTES:
1.
During the execution of this function, all other functions are disabled.
2.
You are advised to use this function to gradually activate the heating function via the radiant panels
(this procedure should be carried out at the start of the season).
3.
If the relative function is activated (paragraph 8.3), the value of these parameters will be stored in the
memory and automatically reset after any possible voltage failure.
7.13.
Activating the defrost cycle (Manual defrost)
After accessing the "Manual defrost" function, you can
activate or deactivate the command for forced execu-
tion of a defrost cycle. Make your selection, then press
"OK" to confirm.
30
ir r m val
Off
ir
at r ta
OK
Floor debug: On
Segments: 2
Period 1 temp: 25°C
Segment time: 12H
T of segment: 5°C
Manual defrost
Off
On
OK
Ca c l
Start
Cancel