4
Customising Settings for Your Home
<[Room sensor settings]>
For room sensor settings it is important to choose the correct room sensor de-
pending on the heating mode the system will operate in.
1. From the Initial settings menu select Room sensor settings.
2. When 2-zone temperature control is active and wireless remote controllers
are available, from Room RC zone select screen, select zone No. to assign to
each remote controller.
3. From Sensor setting screen, select a room sensor to be used for monitoring
the room temperature from Zone1 and Zone2 separately.
Corresponding initial settings room sensor
Control option
(Website manual)
A
Room RC1-8 (one each for
Zone1 and Zone2)
B
C
Main remote controller
D
* Not specified (if a field-supplied room thermostat is used)
Room RC1-8 (one each for Zone1 and Zone2) (if a wireless remote controller
is used as a room thermostat)
4. From Sensor setting screen, select Time/Zone to make it possible to use differ-
ent room sensors according to the time schedule set in the Select Time/Zone
menu. The room sensors can be switched up to 4 times within 24 hours.
Domestic Hot Water (DHW)/Legionella Prevention
The domestic hot water and legionella prevention menus control the operation of
DHW tank heat ups.
<Eco mode>
DHW mode can run in either 'Normal' or 'Eco' mode. Normal mode will heat the
water in the DHW tank more quickly using the full power of the heat pump. Eco
mode takes a little longer to heat the water in the DHW tank but the energy used
is reduced. This is because heat pump operation is restricted using signals from
the FTC based on measured DHW tank temperature.
Note: The actual energy saved in Eco mode will vary according to outdoor
ambient temperature.
Return to the DHW/legionella prevention menu.
Forced DHW
The forced DHW function is used to force the system to operate in DHW mode. In
normal operation the water in the DHW tank will be heated either to the set tem-
perature or for the maximum DHW time, whichever occurs first. However should
there be a high demand for hot water 'Forced DHW' function can be used to pre-
vent the system from routinely switching to space heating/cooling and continue to
provide DHW tank heating.
Forced DHW operation is activated by pressing button F1 and Back button in the
'Option Screen'. After DHW operation finishes, the system will automatically re-
turn to normal operation. To cancel forced DHW operation hold down button F1 in
the 'Option Screen'.
Zone1
Zone2
*
TH1
*
*
*
*
Time/Zone schedule setting screen
en
6