Airwell FDM R32 Manuel D'installation page 21

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

7. INFORMATION SERVICING
the charge size is in accordance with the room size within which the refrigerant containing parts are installed;
 
 
the ventilation machinery and outlets are operating adequately and are not obstructed;
if an indirect refrigerating circuit is being used, the secondary circuits shall be checked for the presence of
refrigerant; marking to the equipment continues to be visible and legible.
marking and signs that are illegible shall be corrected;
refrigeration pipe or components are installed in a position where they are unlikely to be exposed to any
substance which may corrode refrigerant containing components, unless the components are constructed of
materials which are inherently resistant to being corroded or are suitably protected against being so corroded.
7.9 CHECKS TO ELECTRICAL DEVICES
Repair and maintenance to electrical components shall include initial safety checks and component inspection
procedures. If a fault exists that could compromise safety, then no electrical supply shall be connected to the
circuit until it is satisfactorily dealt with. If the fault cannot be corrected immediately but it is necessary to continue
operation, and adequate temporary solution shall be used. This shall be reported to the owner of the equipment
so all parties are advised.
Initial safety checks shall include:
that capacitors are discharged: this shall be done in a safe manner to avoid possibility of sparking
that there no live electrical components and wiring are exposed while charging, recovering or purging the system;
that there is continuity of earth bonding.
7.10 REPAIRS TO SEALED COMPONENTS
10.1 During repairs to sealed components, all electrical supplies shall be disconnected from the equipment being
worked upon prior to any removal of sealed covers, etc. If it is absolutely necessary to have an electrical
supply to equipment during servicing, then a permanently operating form of leak detection shall be located
at the most critical point to warn of a potentially hazardous situation.
10.2 Particular attention shall be paid to the following to ensure that by working on electrical components, the
casing is not altered in such a way that the level of protection is affected.This shall include damage to
CAUTION
cables, excessive number of connections, terminals not made to original specification, damage to seals,
incorrect fitting of glands, etc.
Ensure that apparatus is mounted securely.
Ensure that seals or sealing materials have not degraded such that they no longer serve the purpose of
preventing the ingress of flammable atmospheres. Replacement parts shall be in accordance with the
manufacturer s specifications.
NOTE: The use of silicon sealant may inhibit the effectiveness of some types of leak detection equipment.
Instrinsically safe components do not have to be isolated prior to working on them.
7.11 REPAI TO INTRINSICALLY SAFE COMPONENTS
Do not apply any permanent inductive or capacitance loads to the circuit without ensuring that this will not
exceed the permissible voltage and current permitted for the equipment in use. Intrinscially safe components are
the only types that can be worked on while live in the presence of a flammable atmosphere. The test apparatus
shall be at the correct rating. Replace components only with parts specified by the manufacturer. Other parts may
result in the ignition of refrigerant in the atmosphere from a leak.
GB-20

Publicité

Table des Matières
loading

Table des Matières