Shielding And Cable Routing - Balluff BTL BNC 00 B15A 010-000S92 Série Notice D'utilisation

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 41
BTL BNC_ 00- _ _ _ _ -B15A _010-000S92 / BTL ZNC_ 00- _ _ _ _ -B15A _010-000S92
Magnetostrictive Linear Position Sensor – Rod Style
5
Installation and connection (continued)
5.4

Shielding and cable routing

Defined ground!
The BTL and the control cabinet must be at the
same ground potential.
Shielding
Observe the following instructions to ensure
electromagnetic compatibility (EMC):
Connect BTL and controller using a shielded cable.
Shielding: Braided copper shield with minimum 85%
coverage.
Shield is internally connected to connector housing.
Magnetic fields
The position measuring system is a magnetostrictive
system. Ensure that there is sufficient distance between
the BTL and the transducer/holding cylinder and strong,
external magnetic fields.
Cable routing
Do not route the cable between the BTL, controller, and
power supply near high voltage cables (inductive stray
noise is possible).
The cable must be routed tension-free.
Cable length
BTL ...-B15AA/A1...
BTL ...-B15AE/A5...
Prerequisite: Construction, shielding and routing preclude the effect of
1)
any external noise fields.
Tab. 5-3:
BTL cable lengths
www.balluff.com
Max. 30 m
1)
Max. 100 m
1)
english
11

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Btl znc 00 b15a 010-000s92 série

Table des Matières