Parameter list
Line
Function, display
Block "Space heating"
Heating limit for
61
NORMAL heating
(ECO day)
Heating limit for
62
REDUCED heating
(ECO night)
Building time con-
63
stant
Quick setback
64
Room temperature
65
source
Type of optimization
66
Maximum heating-
67
up time
Building Technologies
Factory setting
Setting
(Range)
17.0 °C
(--.- / −5.0...+25.0)
...................
5.0 °C
(--.- / −5.0...+25.0)
...................
20 h
(0...50)
......................
1
(0 / 1)
.........................
A
(0 / 1 / 2 / 3 / A)
.........................
0
(0 / 1)
.........................
00:00 h
(00:00...42:00)
......................
74 319 0617 0 a
Explanations, notes and tips
Setting --.- = function disabled
°C
Setting --.- = function disabled
°C
Light = 10 h
h
Medium = 25 h
Heavy = 50 h
0 = no quick setback
1 = quick setback
0 = no room temperature sen-
sor present
1 = room unit at terminal A6
2 = room temperature sensor at
terminal B5
3 = mean value of the two units
at terminals A6 and B5
A = automatic selection
0 = optimization with room
model
1 = optimization with room tem-
perature sensor/room unit
(setting 0 only allows optimum
start control)
Maximum forward shift for
h
switching on before start of
occupancy
Setting 00:00 = optimization of
switching on disabled
17.04.2008
en
33/180